5-58
745 Transformer Management Relay
GE Power Management
5.6 S4 ELEMENTS
5 SETPOINTS
5
b) WINDING 1 (2/3) GROUND INSTANTANEOUS OVERCURRENT 1
c) WINDING 1 (2/3) GROUND INSTANTANEOUS OVERCURRENT 2
The messages that follow are identical to those described for GROUND INSTANTANEOUS
OVERCURRENT 1.
y
W1 GND INST OC 1
y
[ENTER] for more
This message indicates the start of the section describing the characteristics
of the first level of
GROUND INSTANTANEOUS OVERCURRENT
protection for
Winding 1 (2/3). To continue with these setpoints press
, or press
to go to the next section.
W1 GROUND INST OC 1
FUNCTION: Disabled
Range: Disabled / Enabled
W1 GROUND INST OC 1
TARGET: Latched
Range: Self-reset / Latched / None
Select
None
to inhibit the display of the target message when the element
operates. Thus an element whose “target type” is
None
will never disable the
LED self-test feature because can not generate a displayable target
message.
W1 GROUND INST OC 1
PICKUP: 10.00 x CT
Range: 0.05 to 20.00 (steps of 0.01)
Enter the level of ground current (in units of relay nominal current) above
which the W1 (2/3) ground instantaneous overcurrent 1 element will pickup
and start the delay timer.
W1 GROUND INST OC 1
DELAY: 0 ms
Range: 0 to 60000 (steps of 1)
Enter the time that the ground current must remain above the pickup level
before the element operates.
W1 GROUND INST OC 1
BLOCK: Disabled
Range: Disabled / Logc Inpt 1 (2-16) /Virt Inpt 1 (2-16) / Output Rly 1 (2-8) /
SelfTest Rly / Virt Outpt 1 (2-5)
y
W1 GND INST OC 2
y
[ENTER] for more
This message indicates the start of the section describing the characteristics
of the second level of
GROUND INSTANTANEOUS OVERCURRENT
protection for
Winding 1 (2/3). To continue with these setpoints press
, or press
to go to the next section.
E N TE R
M E SSA G E
E N TE R
M E SSA G E
NOTE
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...