5-38
745 Transformer Management Relay
GE Power Management
5.4 S2 SYSTEM SETUP
5 SETPOINTS
5
5.4.7 VOLTAGE INPUT
The 745 provides a voltage input for the purposes of energization detection (for the ENERGIZATION INHIBIT
feature of the percent differential element), overexcitation protection (the VOLTS-PER-HERTZ 1 and 2 func-
tions), and frequency protection (the UNDERFREQUENCY, the FREQUENCY DECAY and the OVERFRE-
QUENCY functions). Note that the frequency elements will use Winding 1, phase A current input if voltage is
not available.
y
VOLTAGE INPUT
y
[ENTER] for more
This message indicates the start of the
VOLTAGE INPUT
section. To continue
with these setpoints press
, or press
to go to the next
section.
VOLTAGE SENSING:
Disabled
Range: Disabled / Enabled
Enter
Enabled
when connecting a voltage transformer to this input.
VOLTAGE INPUT
PARAMETER: W1 Van
Range: W1 Van / W1 Vbn / W1 Vcn / W1 Vab / W1 Vbc / W1 Vca / W2 Van
/ W2 Vbn / W2 Vcn / W2 Vab / W2 Vbc / W2 Vca / W3 Van / W3 Vbn
/ W3 Vcn / W3 Vab / W3 Vbc / W3 Vca
Enter the winding and phase of the voltage connected to the voltage input.
NOMINAL VT SECONDARY
VOLTAGE: 120.0 V
Range: 60.0 to 120.0 (steps of 0.1)
Enter the nominal secondary voltage (in volts) of the voltage transformer.
VT RATIO:
1000:1
Range: 1 to 5000 (steps of 1)
Enter the ratio of the voltage transformer.
E N T E R
M E SSA G E
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...