GE Power Management
745 Transformer Management Relay
8-37
8 COMMUNICATIONS
8.3 MODBUS MEMORY MAP
8
TRANSFORMER
continued
1102
Transformer Type
---
---
---
F28
3 = Y/d30°
1103
Rated Winding Temperature Rise
---
---
---
F37
1 = 65°C (oil)
1104
Type of Cooling: Oil Immersed
---
---
---
F39
0 = 0A
1105
Load Loss at Rated Load (2 registers)
1 to 20000
1
kW
F101
1250 kW
1107
No-Load Loss
0.1 to 2000
0.1
kW
F90
1250=125.0 kW
1108
Top Oil Rise Over Ambient (at rated load)
1 to 200
1
°C
F1
10°C
1109
Transformer Thermal Capacity
0.00 to 200.00
0.01
kWh/°C
F3
100=1.00 kWh/°C
110A
Winding Time Constant: Oil-Immersed
0.25 to 15.00
0.01
minutes
F3
200 = 2.00 min
110B
Type of Cooling: Dry
-
-
-
F100
0=sealed self-cooled
110C
Thermal Time Constant: Dry
0.25 to 15.00
0.01
minutes
F3
200 = 2.00 min
110D
Set Initial Accumulated Loss of Life
0 to 20000
1
hrs x 10
F1
0 hours
110E
Frequency Tracking
---
---
---
F30
1 = Enabled
110F
Reserved
↓
↓
↓
↓
↓
↓
↓
111F
Reserved
WINDING 1
1120
Winding 1 Nominal Phase-to-Phase Voltage
1 to 20000
---
kV
F90
220.0 kV
1121
Winding 1 Rated Load
1 to 20000
---
MVA
F90
1000 = 100 MVA
1122
Winding 1 Phase CT Primary
1 to 50000
1
:1 or :5 A
F1
500 A
1123
Winding 1 Ground CT Primary
1 to 50000
1
:1 or :5 A
F1
500 A
1124
Winding 1 Series 3-Phase Resistance
0.001 to 50.000
0.001
Ω
F53
10700 = 10.7
Ω
1125
Reserved
↓
↓
↓
↓
↓
↓
↓
112F
Reserved
WINDING 2
1130
Winding 2 Nominal Phase-to-Phase Voltage
1 to 20000
---
kV
F90
690 = 69.0 kV
1131
Winding 2 Rated Load
1 to 20000
---
MVA
F90
1000 = 100 MVA
1132
Winding 2 Phase CT Primary
1 to 50000
1
:1 or :5 A
F1
1500 A
1133
Winding 2 Ground CT Primary
1 to 50000
1
:1 or :5 A
F1
1500 A
1134
Winding 2 Series 3-Phase Resistance
0.001 to 50.000
0.001
Ω
F53
2100 = 2.100
Ω
1135
Reserved
↓
↓
↓
↓
↓
↓
↓
113F
Reserved
WINDING 3
1140
Winding 3 Nominal Phase-to-Phase Voltage
1 to 20000
---
kV
F90
690 = 69.0 kV
1141
Winding 3 Rated Load
1 to 20000
---
MVA
F90
1000 = 100 MVA
1142
Winding 3 Phase CT Primary
1 to 50000
1
:1 or :5 A
F1
1500 A
1143
Winding 3 Ground CT Primary
1 to 50000
1
:1 or :5 A
F1
1500 A
1144
Winding 3 Series 3-Phase Resistance
0.001 to 50.000
0.001
Ω
F53
2100 = 2.100
Ω
1145
Reserved
↓
↓
↓
↓
↓
↓
↓
Table 8–6: 745 MEMORY MAP (Sheet 21 of 57)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...