GE Power Management
745 Transformer Management Relay
8-65
8 COMMUNICATIONS
8.3 MODBUS MEMORY MAP
8
WINDING 2
CURRENT
DEMAND
23D0
Winding 2 Current Demand Function
---
---
---
F30
0 = Disabled
23D1
Winding 2 Current Demand Target
---
---
---
F46
0 = Self-reset
23D2
Winding 2 Current Demand Pickup
---
---
A
F79
400 A
23D3
Winding 2 Current Demand Block
---
---
---
F87
0 = Disabled
23D4
Reserved
↓
↓
↓
↓
↓
↓
↓
23DF
Reserved
WINDING 3
CURRENT
DEMAND
23E0
Winding 3 Current Demand Function
---
---
---
F30
0 = Disabled
23E1
Winding 3 Current Demand Target
---
---
---
F46
0 = Self-reset
23E2
Winding 3 Current Demand Pickup
---
---
A
F80
400 A
23E3
Winding 3 Current Demand Block
---
---
---
F87
0 = Disabled
23E4
Reserved
↓
↓
↓
↓
↓
↓
↓
23EF
Reserved
XFORMER
OVERLOAD
23F0
Transformer Overload Function
---
---
---
F30
0 = Disabled
23F1
Transformer Overload Target
---
---
---
F46
0 = Self-reset
23F2
Transformer Overload Pickup
50 to 300
1
% rated
F1
208% rated
23F3
Transformer Overload Delay
0 to 60000
1
s
F1
10 s
23F4
Transformer Overload Block
---
---
---
F87
0 = Disabled
23F5
Transformer Overtemperature Alarm Signal
---
---
---
F88
0 = Disabled
23F6
Reserved
↓
↓
↓
↓
↓
↓
↓
23FF
Reserved
AGING
FACTOR
LIMIT
2400
Aging Factor Limit Function
---
---
---
F30
0 = Disabled
2401
Aging Factor Limit Target
---
---
---
F46
0 = Self-reset
2402
Aging Factor Limit Pickup
1.1 to 10.0
0.1
--
F2
20 = 2.0
2403
Aging Factor Limit Delay
0 to 60000
1
minutes
F1
10 minutes
2404
Aging Factor Limit Block
---
---
---
F87
0 = Disabled
2405
Reserved
↓
↓
↓
↓
↓
↓
↓
240F
Reserved
TAP CHANGER
FAILURE
2410
Tap Changer Failure Function
---
---
---
F30
0 = Disabled
2411
Tap Changer Failure Target
---
---
---
F46
0 = Self-reset
2412
Tap Changer Failure Delay
0 to 600.00
0.01
s
F3
500 = 5.00 s
2413
Tap Changer Failure Block
---
---
---
F87
0 = Disabled
2414
Reserved
↓
↓
↓
↓
↓
↓
↓
3FFF
Reserved
Table 8–6: 745 MEMORY MAP (Sheet 49 of 57)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...