GE Power Management
745 Transformer Management Relay
8-63
8 COMMUNICATIONS
8.3 MODBUS MEMORY MAP
8
WINDING 3
THD LEVEL
2340
Winding 3 THD Level Function
---
---
---
F30
0 = Disabled
2341
Winding 3 THD Level Target
---
---
---
F46
0 = Self-reset
2342
Winding 3 THD Level Min. Operating Current
0.03 to 1.00
0.01
×
CT
F3
10 = 0.10
×
CT
2343
Winding 3 THD Level Pickup
0.1 to 50.0
0.1
% ƒo
F2
500 = 50.0%
2344
Winding 3 THD Level Delay
0 to 60000
1
s
F1
10 s
2345
Winding 3 THD Level Block
---
---
---
F87
0 = Disabled
2346
Reserved
↓
↓
↓
↓
↓
↓
↓
234F
Reserved
WINDING 1
HARMONIC
DERATING
2350
Winding 1 Harm Derating Function
---
---
---
F30
0 = Disabled
2351
Winding 1 Harm Derating Target
---
---
---
F46
0 = Self-reset
2352
Winding 1 Harm Derating Min. Operating Current
0.03 to 1.00
0.01
×
CT
F3
10 = 0.10
×
CT
2353
Winding 1 Harm Derating Pickup
0.01 to 0.98
0.01
---
F3
90 = 0.90
2354
Winding 1 Harm Derating Delay
0 to 60000
1
s
F1
10 s
2355
Winding 1 Harm Derating Block
---
---
---
F87
0 = Disabled
2356
Reserved
:
:
235F
Reserved
WINDING 2
HARMONIC
DERATING
2360
Winding 2 Harm Derating Function
---
---
---
F30
0 = Disabled
2361
Winding 2 Harm Derating Target
---
---
---
F46
0 = Self-reset
2362
Winding 2 Harm Derating Min. Operating Current
0.03 to 1.00
0.01
×
CT
F3
10 = 0.10
×
CT
2363
Winding 2 Harm Derating Pickup
0.01 to 0.98
0.01
---
F3
90 = 0.90
2364
Winding 2 Harm Derating Delay
0 to 60000
1
s
F1
10 s
2365
Winding 2 Harm Derating Block
---
---
---
F87
0 = Disabled
2366
Reserved
↓
↓
↓
↓
↓
↓
↓
236F
Reserved
WINDING 3
HARMONIC
DERATING
2370
Winding 3 Harm Derating Function
---
---
---
F30
0 = Disabled
2371
Winding 3 Harm Derating Target
---
---
---
F46
0 = Self-reset
2372
Winding 3 Harm Derating Min. Operating Current
0.03 to 1.00
0.01
×
CT
F3
10 = 0.10
×
CT
2373
Winding 3 Harm Derating Pickup
0.01 to 0.98
0.01
---
F3
90 = 0.90
2374
Winding 3 Harm Derating Delay
0 to 60000
1
s
F1
10 s
2375
Winding 3 Harm Derating Block
---
---
---
F87
0 = Disabled
2376
Reserved
↓
↓
↓
↓
↓
↓
↓
237F
Reserved
Table 8–6: 745 MEMORY MAP (Sheet 47 of 57)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...