GE Power Management
745 Transformer Management Relay
5-43
5 SETPOINTS
5.5 SETPOINTS S3 LOGIC INPUTS
5
5.5 SETPOINTS S3 LOGIC INPUTS
5.5.1 DESCRIPTION
The 745 has two types of digital inputs:
Logic Inputs
have physical terminals for connecting to external con-
tacts.
Virtual Inputs
, on the other hand, although providing the same function as logic inputs, have no physical
external connections: a setpoint defines the state of each in terms of “ON” or “OFF”.
There are 16 of each of logic inputs and virtual inputs. The state (‘asserted’ or ‘not asserted’) of each logic or
virtual input can be used to cause any of a variety of predefined logic functions, such as protection element
blocking, energization detection, etc. In addition, any logic or virtual input can be used as an input in Flex-
Logic™ equations to implement custom schemes.
5.5.2 LOGIC INPUTS
yy
SETPOINTS
yy
S3 LOGIC INPUTS
This message indicates the start of setpoints page
S3 LOGIC INPUTS
. Press
to view the contents of this page or
to go to the next page.
y
LOGIC INPUTS
y
[ENTER] for more
This message indicates the start of the
LOGIC INPUTS
section. To continue
these setpoints, press
, or press
to go to the next section.
y
LOGIC INPUT 1
y
[ENTER] for more
This message indicates the start of the logic input 1 (2-16) setpoints. To
continue with these setpoints, press
, or press
to go to the
next section.
INPUT 1 FUNCTION
Disabled
Range: Disabled / Enabled
Select ‘Enabled’ if this logic input is to be used. Selecting
Disabled
will never
allow this logic input to achieve the ‘Asserted’ (or signaling) state.
INPUT 1 TARGET:
Self-Reset
Range: None / Latched / Self-Reset
Chose
None
to inhibit the display of the target message when the input is
asserted. Thus an input whose “target type” is
None
will never disable the
LED self-test feature because cannot generate a displayable target
message.
INPUT 1 NAME:
Logic Input 1
Range: 18 alphanumeric characters
Press
to begin editing the name of the logic input. The text may be
changed from
Logic Input 1
one character at a time, using
/
.
Press
to store the edit and advance to the next character position.
INPUT 1 ASSERTED
STATE: Closed
Range: Open / Closed
Select
Closed
as the input asserted state when connected to a normally open
contact (where the signaling state is closed). Select
Open
when connected to
a normally closed contact (where the signaling state is open).
M E SSA G E
S ET PO INT
EN T E R
M E SS A G E
E N TE R
M E SSA G E
E N TE R
V AL U E
V A LU E
E N TE R
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...