Function
Code
Parameter
Name
Setting Range
Default
Property
PC.51
Reference 0
source
0: Set by PC.00
1: FIV
2: FIC
3: reserved
4: PULSE setting
5: PID
Set by preset frequency
(P010), modified via terminal UP/DOWN
0
☆
Group PD: Communication Parameters
PD.00
Baud rate
Unit's digit: MODBUS
0: 300BPS
1: 600BPS
2: 1200BPS
3: 2400BPS
4: 4800BPS
5: 9600BPS
6: 19200BPS
7: 38400BPS
8: 57600BPS
9: 115200BPS
Ten's digit: Reserved
Hundred's digit: Reserved Thousand's digit: Reserved
0005
☆
PD.01
Data format
0: No check, data format <8,N,2>
1: Even parity check, data format <B,E,1>
2: Odd Parity check, data format <B,O,1>
3: No check, data format <8,N,1> Valid for Modbus
3
☆
PD.02
Local address 1-247, 0: Broadcast address
1
☆
PD.03
Response delay 0ms ~ 20ms
2
☆
PD.04
Communication
timeout
0.0 (invalid ), 0.1s ~ 60.0s
0.0
☆
PD.05
Modbus protocol
selection
Unit's digit: Modbus protocol
0: Non-standard Modbus protocol
1: Standard Modbus protocol
Ten's digit: reserved
1
☆
PD.06
Communication
reading current
resolution
0: 0.01A
1: 0.1A
0
☆
Group PE: Reserved
Group PP: User-Defined Function Codes
PP.00
User password 0 ~ 65535
0
☆
PP.01
Restore default
settings
0: No operation
01: Restore factory settings except motor parameters
02: Clear records
0
★