The parameters are set as below:
Terminal
Set value
Function Description
Sx
1
Forward RUN enabled(FWD)
Sy
2
Reverse RUN (REV)
Sn
3
Three-line control
Sn terminals must be closed when there is a need to run, Sn terminals, produced by Sx pulse rising along the motor running signal,
the state of the Sy produce motor direction signals.
When there is a need to stop, by disconnecting Sn terminal signal to realize. Among them, the Sx, Sy, Sn is S1 -
S4, FWD,REV multi
function input terminals, Sx is the pulse effective, Sy, Sn are the level effective.
Figure 4-10-2 Setting of three-line mode 2
P5.12
Terminal UP/DOWN changing rate
Default
1.00Hz/s
Setting Range
10.01Hz/s ~ 65.535Hz/s
When it is used to set terminal UP/DOWN to adjust the set frequency .Frequency changing rate is the frequency variation per
second.
If P0.22 (Frequency reference resolution) is 2, the setting range is 0.001-65.535 Hz/s.
If P0.22 (Frequency reference resolution) is 1, the setting range is 0.01-655.35 Hz/s.
P5.13
Fl curve 1 minimum Input
Default
0.00V
Setting Range
0.00V ~P5.15
P5.14
Corresponding setting of Fl curve 1 minimum
input
Default
0.0%
Setting Range
-100.00% ~ 100.0%
P5.15
Fl curve 1 maximum input
Default
10V
Setting Range
P5.13 ~10.00V
P5.16
Corresponding setting of Fl curve 1 maximum
input
Default
100%
Setting Range
-100.00%~100.0%
P5.17
Fl curve 1 filter time
Default
0.10s
Setting Range
0.00s ~10.00s
These parameters are used to define the relationship between the analog input voltage and the corresponding setting. When the
analog
input voltage exceeds the maximum value (P5.15), the analog voltage maximum value is calculated by •maximum inpu
t.
When the analog input voltage is less than the setting minimum input (P5.13), the value set in P5.34 (Setting for Fl less than
minimum input) is calculated by the minimum input or 0.0%
When the analog input is current input, 20mA current corresponds to 1OV voltage.4mA current corresponds to 2V voltage.
Fl input filter time is used to set the software filter time of Fl. If the analog input is liable to interference, increase the filter lime
value of this parameter to stabilize the detected analog Input.
However, increase of the Fl curve 1 filter time will slow the response of analog detection. Set this parameter properly based on
actual conditions.
In different applications, 100% of analog input corresponds to different nominal values. For details, refer to the description of
different applications.
Two typical setting examples are shown in the following figure.