116
Elmark Automatyka S.A.
ul. Niemcewicza 76, 05-075 Warszawa, tel. (+48) 22 773 79 37; [email protected]; www.elmark.com.pl
NIP: 5252072585; KRS: 0000803828, Sąd Rejonowy dla M-St. Warszawy, XIV Wydział Gosp. KRS; Kapitał Zakładowy 525.000 zł, w pełni opłacony
Function
Code
Parameter
Name
Setting Range
Default
Property
PA.22
PID initial value
holding time
0.00 ~ 650.00s
0.00s
☆
PA.23
Maximum
deviation between
two PID outputs in
forward
0.00% ~ 100.00%
1.00%
☆
PA.24
Maximum
deviation between
two PID outputs in
reverse
0.00% ~ 100.00%
1.00%
☆
PA.25
PID integral
property
Unit's digit: Integral separated
0:lnvalid
1:valid
Ten's digit: Whether to stop integral operation when the output reaches
0:Continue integral operation
1:Stop integral operation
00
☆
PA.26
Detection value of
PID feedback
loss
0.0%: Not judging feedback loss
0.1% ~ 100.0%
0.0%
☆
PA.27
Detection time of
PID feedback loss
0.0s ~ 20.0s
0.0s
☆
PA.28
PID operation at
stop
0: No PID operation at stop
1: PID operation at stop
0
☆
Group Pb: Swing Frequency, Fixed Length and Count
Pb.00
Swing frequency
setting mode
0: Relative to the central frequency
1: Relative to the maximum
frequency
0
☆
Pb.01
Swing frequency
amplitude
0.0% ~ 100.0%
0.0%
☆
Pb.02
Jump frequency
amplitude
0.0% ~ 50.0%
0.0%
☆
Pb.03
Swing frequency
cycle
0.1s ~ 3000.0s
10.0s
Pb.04
Triangular wave
rising time
coefficient
0.1% ~ 100.0%
50.0%
Pb.05
Set length
0m ~ 65535m
1000m
Pb.06
Actual length
0m ~ 65535m
0m
Pb.07
Number of pulses
per meter
0.1 ~ 6553.5
100.0
Pb.08
Set count value 1 ~ 65535
1000
Pb.09
Designated count
value
1 ~ 65535
1000
Summary of Contents for elmatic ED2000
Page 1: ......