Function
Code
Parameter
Name
Setting Range
Default
Property
P5.03
S2 function
selection
26: Counter reset
27: Length count input
28: Length reset
29: Torque control prohibited
30: Pulse input (enabled only for S3)
31: Reserved
32: Immediate DC braking
33: Normally closed (NC)input of external fault
34: Frequency modification forbidden
35: Reverse PID action direction
36: External STOP terminal 1
37: Command source switchover terminal 2
38: PID integral pause
39: Switchover between main frequency source X and preset frequency
40: Switchover between auxiliary frequency source Y and preset frequency
41: Motor selection terminal 1
42: Motor selection terminal 2
43: PID parameter switchover
44: Reserved
45: Reserved
46: Speed control/Torque control switchover
47: Emergency stop
48: External STOP terminal 2
49: Deceleration DC braking
50: Clear the current running time
51-69: Reserved
12
★
P5.04
S3 function
selection
13
★
P5.05
S4 function
selection
0
★
P5.10
S filter time
0.000s ~ 1.000s
0.010s
☆
P5.11
Terminal
command mode
0: Two-line mode 1
1: Two-line mode 2
2: Three-line mode 1
3: Three-line mode 2
0
★
P5.12
Terminal UP/
DOWN rate
0.001Hz/s ~ 65.535Hz/s
1.00Hz/s
☆
P5.13
Fl curve 1
minimum input
0.00V ~ P5.15
0.00V
☆
P5.14
Corresponding
setting of Fl curve
1 minimum input
-100.0% ~ +100.0%
0.0%
☆
P5.15
Fl curve 1
maximum input
P5.13 ~ +10.00V
10.00V
☆
P5.16
Corresponding
setting of Fl curve
1 maximum input
-100.0% ~ +100.0%
100.0%
☆
P5.17
Fl curve 1 filter
time
0.00s ~ 10.00s
0.10s
☆
P5.18
Fl curve 2
minimum input
0.00V ~ P5.20
0.00V
☆
P5.19
Corresponding
setting of Fl curve
2 minimum input
-100.0% ~ +100.0%
0.0%
☆