2
Continue to run
Ten's digit
Reserved
Hundred's
digit
Power output phase loss (LO) (the
same as unit's digit)
Thousand's digit
External equipment fault (EF) (the
same as unit's digit)
Ten
thousand's digit
Communication fault (CE) (the same as unit's digit)
P9.48
Fault protection action selection 2
Default
00000
Setting Range
Unit's digit
Reserved
0
Coast to stop
1
Switch over to V/F control, stop according to the stop mode
2
Switch over to V/F control, continue to run
Ten's digit
function code read-write
abnormal(EEP)
0
Coast to stop
1
stop according to the stop mode
Hundred's digit
Reserved
Thousand's
digit
Reserved
Ten thousand's
digit
Accumulative running time reached (END1) (the same as unit's digit
in
P9.47)
P9.49
Fault protection action selection 3
Default
00000
Setting Range
Unit's digit
reserved
Ten’s digit
reserved
Hundred's digit
Accumulative power-on time reached
(END2) (the same as unit's digit in P9.47)
Thousand's digit
Load becoming O (LOAD)
0
Coast to stop
1
stop according to the stop mode
2
Continue to run at 7% of rated motor
frequency and resume to the set frequency if the load recovers
Ten
thousand's digit
PID feedback lost during running (PIDE)
(the same as unit's digit in P9.47)
P9.50
Reserved
If "Coast to stop" is selected, the AC drive displays error code and directly stops.
If "Stop according to the stop mode" is selected, the AC drive displays alarm code and stops according to the stop mode. After
stopping, the AC drive displays error code.
If "Continue to run• i
s selected, the AC drive continues to run and displays alarm code. The running frequency is set in P9.54.
P9.54
Frequency selection for continuing to run
Default
0
Setting Range
0
Current running frequency
1
Set frequency
2
Frequency upper limit
3
Frequency lower limit
4
Backup frequency upon abnormality