31
FIV input limit
exceeded
If FIV input is larger than the value of P9.46 (FIV input voltage upper limit) or lower than
the value of P9.45 (FIV input voltage lower limit), the terminal
outputs ON.
32
Load becoming 0
If the load becomes 0, the terminal outputs ON.
33
Reverse running
If the AC drive is in the reverse running state, the terminal outputs ON.
34
Zero current
stats
Refer to the descriptions of PS.28 and PB.29.
35
Module temperature reached
If the heatsink temperature of the inverter module
(P7.07) reaches the set module temperature threshold (PB.47), the terminal outputs
ON.
36
Software current limit
exceeded
Refer to the descriptions of PS.38 and PB.37.
37
Frequency lower limit
reached (having
output at stop)
If the running frequency reaches the lower limit, the terminal becomes ON. In the stop
state, the signal is still ON.
38
Alarm output
If a fault occurs on the AC drive and the AC drive continues to run, the terminal outputs
the alarm
signal.
39
Reserved
Reserved
40
Current running time
reached
If the current running time of AC drive exceeds the value of PB.53, the terminal outputs
ON.
P6.07
FOV output function selection
Default
0
P6.08
Reserved
The output range of FOV is 0-10 V or 0-20 mA. The relationship between pulse and analog output ranges and corresponding
functions is listed in the following table.
Table 4-6 Relationship between pulse and analog output ranges and corresponding functions.
Value
Function
Range (Corresponding to Pulse or Analog Output Range 0.0%-100.0%)
0
Running frequency
0 ~ maximum output frequency
1
Set frequency
0 ~ maximum output frequency
2
Output current
0 ~ 2 times of rated motor current
3
Output torque
0 ~ 2 times of rated motor torque
4
Output power
0~2 times of rated power
5
Output voltage
0~1.2 times of rated AC drive voltage
6
Pulse Input
0.01kHz~100.00kHz
7
FIV
0V ~ 10V
8
FIC
0V ~ 10V (or 0~20mA)
9
Reserved
10
Length
0 ~ maximum set length
11
Count value
0 ~ maximum count value
12
Communication
setting
0.0% ~ 100.0%
13
Motor rotational
speed
0 ~ rotational speed corresponding to maximum output frequency
14
Output current
0.0A ~ 1000.0A
15
Output voltage
0.0V ~ 1000.0V