Function
Code
Parameter
Name
Setting Range
Default
Property
P4.13
Voltage source for
V/F separation
0: digital setting(P4.14)
1: FIV
2: FIC
3: Reserved
4: PULSE setting(S3)
5: Multi-reference
6: Simple PLC
7: PID
8: Communication setting
100.0% corresponds to the rated motor voltage.
0
☆
P4.14
Voltage digital
setting for V/F
separation
0v-rated motor voltage
0V
☆
P4.15
Voltage rise time
of V/F separation
0.Os-1000.0s
It indicates the time for the voltage rising from OV to rated
motor voltage.
0.0s
☆
P4.16
Voltage decline
time of V/F
separation
0.0s-1000.0s
It indicates the time for the voltage to decline from rated
motor voltage to 0 V.
0.0s
☆
Group P5: Input Terminals
P5.00
FWD function
selection
No function
1: Forward RUN(FWD)
2: Reverse RUN(REV)
3: Three-line control
4: Forward JOG(FJOG)
5: Reverse JOG(RJOG)
6: Terminal UP
7: Terminal DOWN
8: Coast to stop
9: Fault reset(RESET)
10: RUN pause
11: Normally open (NO) input of external fault
12: Multi-reference terminal 1
13: Multi-reference terminal 2
14: Multi-reference terminal 3
15: Multi-reference terminal 4
16: Terminal 1 for acceleration/ deceleration time selection
17: Terminal 2 for acceleration/ deceleration time selection
18: Frequency source Switchover
19: UP and DOWN setting
clear (terminal, operation panel)
20: Command source switchover terminal
21: Acceleration/Deceleration Prohibited
22: PID pause
23: PLC status reset
24: Swing pause
25: Counter input
1
★
P5.01
REV function
selection
4
★
P5.02
S1 function
selection
9
★