C6.12
Fl curve 5 inflexion 2 input
Default
6.00V
Setting Range
C6.10 ~ C6.14
C6.13
Corresponding setting of Fl curve 5 inflexion 2 input
Default
60.0%
Setting Range
-100.0% ~ 100.0%
C6.14
Fl curve 5 maximum input
Default
10.00V
Setting Range
C6.14 ~ 10.00V
C6.15
Corresponding setting of Fl curve 5 maximum input
Default
100.0%
Setting Range
-100.0% ~ 100.0%
The function of curve 4 and curve 5 is similar to that curve 1 to curve 3, but curve 1 to curve 3 are lines, and curve 4 and curve 5
are 4-point curves, implementing more flexible corresponding relationship. The schematic diagram of curve 4 and curve 5 is shown
in the following figure.
Figure 4-29 Schematic diagram curve 4 and curve 5
When setting curve 4 and curve 5, note that the curve's minimum input voltage, inflexion 1 voltage, inflexion 2 voltage and
maximum voltage must be in increment order.
P5.33 (Fl curve selection) is used to determine how to select curve for FIV to FIC from the five curves.
C6.16
Jump point of FIV input corresponding setting
Default
0.0%
Setting Range
-100.0% ~ 100.0%
C6.17
Jump amplitude of FIV input corresponding setting
Default
0.5%
Setting Range
0.0% ~ 100.0%
C6.18
Jump point of FIC input corresponding selling
Default
0.0%
Setting Range
-100.0% ~ 100.0%
C6.19
Jump amplitude of FIC input corresponding setting
Default
0.5%
Setting Range
0.0% ~ 100.0%
The analog input terminals (FIV to FIC) of the ED2000 all support the corresponding setting jump function, which fixes the analog
input corresponding setting at the jump point when analog input corresponding setting jumps around the jump range.
For example, FIV input voltage jumps around 5.00 V and the jump range is 4.90-5.10V.FIVminimum input 0.00 V corresponds to
0.0% and maximum input 10.00 V corresponds to 100.0%. The detected FIV input corresponding setting varies between 49.0%
and 51.0%. If you set C6.16 to 50.0% and C6.17 to 1.0%, then the obtained stable input FIV input corresponding setting is fixed to
50.0% after the jump function, eliminating the fluctuation effect.
Function Code
Description
Range
Default value
C9.00
PIO Sleep frequency
0 ~ P0.12
00.00 Hz
C9.01
PIO Sleep lime
0 ~ 5000.0S
10.0 S
C9.02
PID wake-up value
0 ~100.0 %
60.0 %
Function Description:
Run, the output frequency <PID sleep frequency (C9.00) and lasted longer than C9.01 and the feedback value> 90% of a given
value. The frequency is reduced to 0, from going to sleep. Sleep feedback <C9.02 * given value, the inverter exits Sleep, the output
frequency is increased. Sleep, temperature less than 42 degrees, the fan will stop.