2.4.1 Control Terminal Description
(1) Input signals
Terminal Name
Function Description
Remarks
FWD
Forward commend input (multi-function input terminals)
Multi-function input terminals S1 - 54, FWD,
REV terminals by reference number of specific
settings, set the terminal and GND closed
effective
REV
Reverse commend input (multi-function
input terminals)
S1
Multi-function input terminals
S2
Multi-function input terminals
S3
High-11peed pulse input terminal (optional)
S4
Multi-function input terminals
FOV
Analog output terminal
0~10V/0~20mA
10V
Frequency setting power
FIV
Analog voltage Input terminal
0~10V
FIC
Analog input terminal
0~ 20mA/0~ 10V
GND
Input signal common
MCM
Optically coupled output common
M01
Multifunctional optical coupling output contacts
RS+
RS485 positive
RS485
communication
RS-
RS485 negative
RA
Relay output contacts (normally open)
RB
Relay output contacts (normally closed)
RC
Relay output contacts RA, RB common
Control panel switch Description:
Switch name
Switch Description
J2
Voltage (0 ~ 10V) / current (0 ~ 20mA) input switch V, FIC short for voltage input; I, FIC short for currant input
J1
Voltage (0 ~ 10V) / current (0 ~ 20mA) output switch V and FOV shorted to voltage output; I and FOV shorting current
output
Control loop distribution NOTES:
(1)
Please let the control signal lines and the main lines, and other power lines, power lines separate traces.
(2)
In order to prevent interference caused by malfunction, use stranded or double-stranded shielded wire line,
specifications for 0.5 - 2mm2
(3)
Make sure that each using terminal to allow conditions, such as: power supply, the maximum current.
(4)
correct ground terminal E, grounding resistance is less than
100Ω.
(5)
each terminal's wiring requirements, the correct selection of accessories such as potentiometers, voltmeter, input power
supplies.
(6)
After completing the wiring correctly and check to make sure it is
correct and then the power can be on.
Summary of Contents for elmatic ED2000