Random PWM depth is set to improve the motor's noise, reduce electromagnetic interference.
C5.04
Fast current limiting open
Default
1
Setting Range
0
Not open
1
Open
Opening fast current limiting can reduce overcurrent fault, make the inverter work normally. Opening fast current limiting for a
long time, can make the inverter overheat, Report a fault CBC.CBC represents fast current limiting fault and need to stop.
C5.05
Current detection compensation
Default
5
Setting Range
0 ~ 100
Used to set current detection compensation, don't recommend to modify.
C5.06
Undervoltage setting
Default
100%
Setting Range
60.0 ~ 140.0 %
Used to set the voltage of inverter's lack voltage fault LU, Different voltage levels of inverter's 100%,corresponding to different
voltages, Respectively single-phase 220V or three-phase 220V: three-phase 380V:350;three-phase 690V:650V.
C5.07
SFVC optimization mode selection
Default
1
Setting Range
0
No optimization
1
Optimization mode 1
2
Optimization mode 2
1: Optimization mode 1
It is used when the requirement on torque control linearity is high.
2: Optimization mode 2
It is used for the requirement on speed stability is high.
Group C6: Fl Curve Setting(FI is FIV or FIC)
C6.00
Fl curve 4 minimum input
Default
0.00V
Setting Range
- 10.00V ~ C6.02
C6.01
Corresponding setting of Fl curve 4 minimum input
Default
0.0%
Setting Range
-100.0% ~ 100.0%
C6.02
Fl curve 4 inflexion 1 input
Default
3.00V
Setting Range
IC6.00~C6.04
C6.03
Corresponding setting of Fl curve 4 inflexion 1 input
Default
30.0%
Setting Range
-100.0 % ~ 100.0%
C6.04
Fl curve 4 inflexion 2 input
Default
6.00V
Setting Range
C6.02 ~ C6.06
C6.05
Corresponding setting of Fl curve 4 inflexion 2 input
Default
60.0%
Setting Range
-100.0% ~ 100.0%
C6.06
Fl curve 4 maximum input
Default
10.00V
Setting Range
C6.06 ~ 10.00V
C6.07
Corresponding setting of Fl curve 4 maximum input
Default
100.0%
Setting Range
-100.0% ~ 100.0%
C6.08
Fl curve 5 minimum input
Default
0.00V
Setting Range
-10.00V ~ C6.10
C6.09
Corresponding setting of Fl curve 5 minimum input
Default
0.0%
Setting Range
-100.0% ~ 100.0%
C6.10
Fl curve 5 inflexion 1 input
Default
3.00V
Setting Range
C6.08 ~ C6.12
C6.11
Corresponding setting of Fl curve 5 inflexion 1 input
Default
30.0%
Setting Range
-100.0% ~ 100.0%