53
Elmark Automatyka S.A.
ul. Niemcewicza 76, 05-075 Warszawa, tel. (+48) 22 773 79 37; [email protected]; www.elmark.com.pl
NIP: 5252072585; KRS: 0000803828, Sąd Rejonowy dla M-St. Warszawy, XIV Wydział Gosp. KRS; Kapitał Zakładowy 525.000 zł, w pełni opłacony
P6.10
FOV zero offset coefficient
Default
10.0%
Setting Range
-100.0% ~ +100.0%
P6.11
FOV gain
Default
1.00
Setting Range
-10.00 ~ +10.00
P6.12
Reserved
P6.13
Reserved
These function codes are used to correct the zero drift of analog output and the output amplitude deviation. They can also be
used to define the desired FOV curve.
If "b" represents zero offset, "k" represents gain, "Y" represents actual output, and "X" represents standard output, the actual
output is: Y = kX + b.
Among them the zero offset coefficient 100% of FOV corresponds to 10V (or 20 mA). The standard output refers to the value
corresponding to the analog output of Oto 10V (or 0 to 20 mA) with no zero offset or gain adjustment.
For example, if the analog output is used as the running frequency, and it is expected that the output is 8V when the frequency at
the maximum frequency is 3V, the gain shall be set to -0.50, and the zero offset shall be set to 80%.
P6.17
M01 output delay time
Default
0.0s
Setting Range
0.0s~3600.0s
P6.18
RA-RB-RC output delay time
Default
0.0s
Setting Range
0.0s~3600.0s
These parameters are used to set the delay time of output terminals M01, relay 1 from status change to actual output.
P6.22
Output terminal valid mode selection
Default
00000
Setting Range
Unit's digit
M01 valid model
0
Positive logic
1
Negative logic
Ten's digit
RA-RB-RC valid mode (0~1, the same as M01)
It is used to definite the logic of output terminals M01,RA,RB,RC.
0: Positive logic
The output terminal is valid when it is connected with GND, and invalid when it is disconnected from GND.
1: Negative logic
The output terminal is invalid when it is connected with GND, and valid when it is disconnected from GND.
Group P7: Operation Panel and Display
P7.00
Output power corrections factor
Default
100.0
Setting Range
0
0.0~200.0
Can correct output power by modifying parameter P7.00, (output power can be viewed through the parameter D0.05)
P7.01 Reserved
P7.02
STOP/RESET key function
Default
1
Setting Range
0
STOP/RESET key enabled only in operation panel control
1
STOP/RESET key enabled in any operation mode