Figure 4-14 FDT level
P8.21
Detection range of frequency reached
Default
0.0%
Setting Range
0.00 ~100% (maximum frequency)
If the AC drive's running frequency is within the certain range of the set frequency, the corresponding M01 terminal becomes ON.
This parameter is used to set the range within which the output frequency is detected to reach the set frequency. The value of
this parameter is a percentage relative to the maximum frequency. The detection range of frequency reached is shown in the
following figure.
P8.22
Jump frequency during the process of acceleration/deceleration
Default
1
Setting Range
0: Disabled
1: Enabled
It is used to set whether the jump frequency is valid during the process of acceleration/deceleration.
When the jump frequency is valid during acceleration/deceleration, and the running frequency is within the frequency jump range,
the actual running frequency will jump over the set frequency jump amplitude (rise directly from the lowest jump frequency to
the highest jump frequency). The following figure shows the diagram when the jump frequency is valid during
acceleration/deceleration.