Appendix A
List of Function Parameters
If PP.00 is set to a non-zero number, parameter protection is enabled. You must enter the correct user password to enter the
menu. To cancel the password protection function, enter with password and set PP.00 to 0.
Parameters menu the user customizes are not protected by password. Group P is the basic function parameters , Group D is to
monitor the function parameters. The symbols in the function code table are described as follows:
“
☆
”
: The parameter can be modified when the AC drive is in either stop or running state.
“
★
”
The parameter cannot be modified when the AC drive is in the running state.
“•”:The
parameter
is
the
actually
measured
value
and
cannot
be
modified.
“*”:The parameter is factory parameter and can be set only by the manufacturer.
Standard Function Parameters
Function
Code
Parameter Name
Setting Range
Default
Property
Group P0: Standard Function Parameters
P0.00
GIP type display
1:G type (constant torque load)
2:Ptype (variable torque load e.g.
Fan and pu,-4))
Model
dependent
★
P0.01
Control mode
selection
0:Voltage/Frequency (V/F) control
1:Sensorless flux vector control (SFVC)
0
★
P0.02
Command source
selection
0:Operation panel control
1:Terminal control
2:Communication control
0
☆
P0.03
Frequency source
superposition
selection
Unit's digit (Frequency source) 0:Main frequency source X
1:X and Y operation(operation relationship determined by ten's digit)
2:Switchover between X and Y 3:Switchover between X and "X and Y
operation" 4:Switchover between Y and "X and Y operation"
Ten's digit (X and Y operation)
0: X+Y
1: X-Y
2: Maximum 3:Minimum
00
☆
P0.04
Main frequency
source X selection
0:Digital setting(P01.0 preset frequency, can modify the UP/DOWN, power
lost don't memory)
1:Digital setting(P0.10 preset frequency, can modify the UP/ DOWN, power
lost memory)
2:FIV
3:FIC
4:Reserved 5:Pulse setting(S3)
6:Multistage instruction 7:Simple PLC
8:PID
9:Communications given
0
★
P0.05
Auxiliary
frequency source
Y
selection
The same as P0.04 (Main frequency source X selection)
0
★