P8.43
Timing duration selection
Default
0
Setting Range
0
P8.44
1
FIV
2
FIC
3
Reserved
100%of analog input corresponds to the value of P8.44
P8.44
Timing duration
Default
0.0 Min
Setting Range
0.0 Min ~ 6500.0 Min
These parameters are used to implement the AC drive timing function.
If P8.42 is set to 1, the AC drive starts to time at startup. When the set timing duration is reached, the AC drive stops automatically
and meanwhile the corresponding M01 outputs ON.
The AC drive starts timing from 0 each lime it starts up and the remaining timing duration can be queried by D0.20.The timing
duration is set in P8.43 and P8.44, in the unit of minute.
P8.45
FIV Input voltage lower limit
Default
3.1V
Setting Range
0.00V ~ P8.46
P8.46
FIV input voltage upper limit
Default
6.8V
Setting Range
P8.45 ~ 10.00V
These two parameters are used to set the limits of the input voltage to provide protection on the AC drive. When the FIV input is
larger than the value of P8.46 or smaller than the value of P8.45, the corresponding M01 becomes ON, indicating that whether
FIV input exceeds the limit.
P8.47
Module temperature
Default
100⁰C
Setting Range
0 ~ 150⁰C
When the heat sink temperature of the AC drive reaches the value of this parameter, the corresponding MD1 becomes ON,
indicating that the module temperature reaches the threshold.
P8.48
Cooling fan control
Default
0
Setting Range
0: Fan working during running
1: Fan working continuously
It is used to set the working mode of the cooling fan. If this parameter is set to D, the fan works when the AC drive is in running
state. When the AC drive stops, the cooling fan works if the heat
sink temperature is higher than 40°C, and stops working if the
heat sink temperature is lower
than 40°C.
If this parameter is set to 1, the cooling fan keeps working after power-on.
P8.49
Wakeup frequency
Default
0.00Hz
Setting Range
Dormant frequency (P8.51) ~ maximum frequency (P0.12)
P8.50
Wakeup delay time
Default
0.0s
Setting Range
0.0s ~6500.0s
P8.51
Dormant frequency
Default
0.00Hz
Setting Range
0.00Hz ~ wakeup frequency (P8.49)
P8.52
Dormant delay time
Default
0.0s
Setting Range
0.0s ~3500.0s
These parameters are used to implement the dormant and wakeup functions in the water supply application.
When the AC drive is in running state, the AC drive enters the dormant state and stops automatically after the dormant delay time
(P8.52) if the set frequency is lower than or equal to the dormant frequency (P8.51).
When the AC drive is in dormant state and the current running command is effective, the AC drives starts up after the wakeup
delay time (P8.50) if the set frequency is higher than or equal to the wakeup frequency (P8.49).