Function
Code
Parameter
Name
Setting Range
Default
Property
P9.55
Backup
frequency upon
abnormality
60.0% ~ 100.0%
100.0%
☆
P9.56
reserved
☆
P9.57
reserved
☆
P9.58
reserved
☆
P9.59
Action selection
at instantaneous
power failure
0: Invalid
1: Decelerate
2: Decelerate to stop
0
☆
P9.60
Action pause
judging voltage at
instantaneous
power failure
0.0%-100.0%
100.0%
☆
P9.61
Voltage rally
judging time at
instantaneous
power failure
0.00s-100.00s
0.50s
☆
P9.62
Action judging
voltage at
instantaneous
power failure
60.0% ~100.0% (standard bus voltage)
80.0%
☆
P9.63
Protection upon
load becoming
0
0: Disabled
1: Enabled
0
☆
P9.64
Detection
level of load
becoming 0
0.0 ~ 100.0%
10.0%
☆
P9.65
Detection time of
load
becoming 0
0.0 ~ 60.0s
1.0s
☆
P9.67
Reserved
☆
P9.68
Reserved
☆
P9.69
Reserved
☆
P9.70
Reserved
☆
Group PA: Process Control PID Function
PA.00 PID setting source
0: PA.01
1: FIV
2: FIC
3: Reserved
4: PULSE setting(S3)
5: Communication setting
6: Multi-reference
0
☆
PA.01
PID digital setting 0.0% ~ 100.0%
50.0%
☆