P9.05
Over currant stall gain
Default
20
Selling Range
0~100
P9.06
Over current stall protective currant
Default
150%
Setting Range
100%~200%
When the output current exceeds the over current stall protective current during acceleration/deceleration of the AC drive, the
AC drive stops acceleration/deceleration and keeps the present running frequency. Alter the output current declines, the AC drive
continues to accelerate/decelerate.
P9.05 (Over current stall gain) is used to adjust the over current suppression capacity of the AC drive. The larger the value is, the
greater the over current suppression capacity will be. In the prerequisite of no over current occurrence, set P9.05 to a small value.
For small-inertia load, the value should be small. Otherwise, the system dynamic response will be slow. For large-inertia load, the
value should be large. Otherwise, the suppression result will be poor and over current fault may occur. If the over current stall
gain is set to 0, the over current stall function is disabled.
P9.07
Short-circuit to ground upon
power-on
Default
1
Setting Range
0
Disabled
1
Enabled
It is used to determine whether to check the motor is short-circuited to ground at power-on of the AC drive. If this function is
enabled, the AC drive's UVW will have voltage output a while alter power-on.
P9.09
Fault auto reset times
Default
0
Setting Range
0 ~ 20
It is used to set the times of fault auto resets if this function is used. After the value is exceeded, the AC drive will remain in the
fault state.
P9.10
M01 action during fault auto reset
Default
1
Setting Range
0.1s ~ 100.0s
It is used to decide whether the M01 acts during the fault auto reset if the fault auto reset function is selected.
P9.11
Time interval of fault auto
Default
1.0s
Setting Range
0.1s ~ 100.0s
It is used to set the waiting time from the alarm of the AC drive to fault auto reset.
P9.12 Reserved
P9.13
Output phase lost protection selection
Default
1
Setting Range
0:Prohibited
1:Permitted
It is used to determine whether to perform output phase loss protection.
P9.14
1
st
fault type
0-99
P9.15
2
nd
fault type
P9.16
3
rd
(latest) fault type