Function
Code
Parameter
Name
Setting Range
Default
Property
P0.06
Auxiliary
frequency source
superposition Y
range selection
0: Relative to the maximum frequency
1: Relative to the main frequency source X
0
☆
P0.07
Auxiliary
frequency source
superposition Y
range
0%-150%
100%
☆
P0.08
Acceleration time
1
0.00s ~ 65000s
Model
dependent
☆
P0.09
Deceleration time
1
0.00s ~ 65000s
Model
dependent
☆
P0.10
Frequency
preset
0.00Hz ~ maximum frequency(P0.12)
50.00Hz
☆
P0.11 Rotation direction
0: Same direction
1: Reverse direction
0
☆
P0.12
Maximum
frequency
50.00Hz ~ 320.00Hz
50.00Hz
★
P0.13
Upper limit
frequency source
0: P0.12
1: FIV
2: FIC
3: Reserved
4: PULSE settings
5: Communication settings
0
★
P0.14
Upper limit
frequency
Frequency lower limit
P0.16~Maximum frequency P0.12
50.00Hz
☆
P0.15
Upper limit
frequency offset
0.00Hz ~ Maximum frequency P0.12
0.00Hz
☆
P0.16
Frequency lower
limit
0.00Hz ~ Upper limit frequency P0.14
0.00Hz
☆
P0.17
Carrier
frequency
1kHz ~ 16.0kHz
Model
dependent
☆
P0.18
Carrier frequency
adjustment with
temperature
0:No
1:Yes
1
☆
P0.19
Acceleration/
Deceleration
time unit
0: 1s
1: 0.1s
2: 0.01s
1
★
P0.21
Frequency offset
of auxiliary
frequency source
for X and
Y operation
0.00Hz ~ Maximum frequency P0.12
0.00Hz
☆
P0.22
Frequency
reference
1:0.1Hz
2:0.01Hz
2
★