Function
Code
Parameter
Name
Setting Range
Default
Property
Group P7:Operation Panel and Display
P7.00
Output power
correction factor
0.0-200.0
100.0
☆
P7.01
Reserved
P7.02
STOP/RESET
key function
0:STOP/RESET key enabled only in operation panel control
1:STOP/RESET key enabled in any operation mode
1
☆
P7.03
LED display
running
parameters 1
0000-FFFF
Bit00: Running frequency 1 (Hz)
Bit01: Set frequency (Hz)
Bit02: Bus voltage (V)
Bit03: Output voltage (V)
Bit04: Output current (A)
Bit05: Output power (kW)
Bit06: Output torque(%)
Bit07: S input status
Bit08: M01 output status
Bit09: FIV voltage (V)
Bit10: FIC voltage (V)
Bit11: Reserved
Bit12: Count value
Bit13: Length value
Bit14: Load speed display
Bit15: PID setting
1F
☆
P7.04
LED display
running
parameters 2
0000-FFFF
Bit00: PID feedback
Bit01: PLC stage
Bit02: Pulse setting frequency(kHz)
Bit03: Running frequency 2 (Hz)
Bit04: Remaining running time Bit05: FIV voltage before correction (V}
Bit06: FIC voltage before correction (V}
Bit07: Reserved
Bit08: Linear speed
Bit09: Current power-on time(Hour)
Bit10: Current running time (Min)
Bit11: Pulse setting frequency(Hz)
Bit12: Communication setting value
Bit13: Reserved
Bit14: Main frequency X display(Hz)
Bit15: Auxiliary frequency Y display (Hz)
0
☆