Chapter4 Detailed Function Description
Group P0: Basic Parameters
P0.00
GIP type display
Default
Model dependent
Setting Range
1
G type (constant torque load)
2
P type (variable torque load e.g. fan and pump)
This parameter is used to display the delivered model and cannot be modified.
1: Applicable to constant torque load with rated parameters specified
2: Applicable to variable torque load (fan and pump) with rated parameters specified
P0.01
Control mode selection
Default
0
Setting Range
0
Voltage/Frequency (V/F) control
1
Sensor less flux vector control (SFVC)
0: Voltage/Frequency (V /F) control
It is applicable to applications with low load requirements or applications where one AC drive operates multiple motors, such as
fan and pump
1:Sensorless flux vector control (SFVC)
It indicates open-
loop vector control, and is applicable to high performance control applications such as machine tool, centrifuge,
wire drawing machine and injection moulding machine. One AC drive can operate only one motor.
Note: If vector control is used, motor auto-tuning must be performed because the advantages of vector control can only be utilized
after correct motor parameters are obtained. Better performance can be achieved by adjusting the motor parameters.
P0.02
Command channel selection
Default
0
Setting Range
0
Operation panel control
1
Terminal control
2
Communication control
It is used to determine the input channel of the AC drive control commands, such as run, stop, forward rotation, reverse rotation
and jog operation. You can input the commands in the following three channels:
0: Operation of panel control
Commands are given by pressing keys RUN and STOP/RESET on the operation panel.
1: Terminal control
Commands are given by means of multifunctional input terminals with functions such as FWD, REV, JOGF, and JOGR.
2: Communication control (Modbus RTU) Commands are given from host computer.
P0.03
Frequency source
Default
00
Setting Range
Unit's digit (Frequency source)
0
Main frequency source X
1
X and Y operation (operation relationship determined by ten's digit)
2
Switchover between X and Y
3
Switchover between X and “X and
Y” “operation"
4
Switchover between Y and "X and Y"
"operation"
Ten's digit (X and Y operation}
0
X+Y
1
X-Y