27
Elmark Automatyka S.A.
ul. Niemcewicza 76, 05-075 Warszawa, tel. (+48) 22 773 79 37; [email protected]; www.elmark.com.pl
NIP: 5252072585; KRS: 0000803828, Sąd Rejonowy dla M-St. Warszawy, XIV Wydział Gosp. KRS; Kapitał Zakładowy 525.000 zł, w pełni opłacony
1
digital setting(P0.10 preset frequency,
can modify the UP/DOWN, power lost memory)
2
FIV
3
FIC
4
Reserved
5
Pulse setting (S3)
6
Multistage instruction
7
PLC
8
PIO
9
Communications given
Auxiliary frequency source with the frequency for a given channel as an independent (i.e. frequency source selection of X to Y
switch), its usage and the main frequency source with X, using the method can be refer to P0.04 related instructions.
When auxiliary frequency source used as a superposition of a given (i.e. frequency source selection of X + Y, X to X + Y switch or Y
to X + Y), the need to pay attention to:
When the auxiliary frequency source for digital timing, preset frequency (P0.10) doesn't work, the user through the keyboard
bring
▲
,
▼
button (or multi-function input terminal of UP and DOWN) on the frequency of adjustment. directly in the main on
the basis of a given frequency adjustment.
1)
When the auxiliary frequency source for analog input given (FIV, FIC) or to the input pulse given, 100% of the input set
corresponding auxiliary frequency source range, can be set by P0.06 and P0.07.
2)
3) When Frequency source is pulse input given similar to analog given. Tip: auxiliary frequency source selection and main
frequency source X, Y can't set to the same channel, namely P0.04 and P0.05 can't set to the same value, otherwise it will be easy
to cause confusion.
P0.06
Auxiliary frequency source superposition
Y
range selection
Default
0
Setting Range
0
Relative to the maximum frequency
1
Relative to the main frequency source X
P0.07
Auxiliary frequency source superposition
Y
Default
0
Setting Range
0%-150%
When selecting frequency source for the superposition of "frequency" (P0.03 set to 1, 3, or 4), these two parameters are used to
determine the adjusting range of auxiliary frequency source.
PO.OS is used to determine the scope of the auxiliary frequency source of the object, the choice of relative to the maximum
frequency, can also be relative to the rate of frequency source X, if choice is relative to the main frequency source, the scope of
the secondary frequency source will change as the change of main frequency X.
P0.08
Acceleration time 1
Default
Model dependent
Setting Range
0.00s-65000s
P0.09
Deceleration time1
Default
Model dependent
Setting Range
0.00s-65000s
Acceleration time refers to the inverter from zero, the deceleration time needed for reference frequency (P0.24 determine).
Deceleration time refers to the inverter from benchmark frequency (P0.24 determine), deceleration down to zero frequency time
required.
P0.10
Frequency preset
Default
50.00 Hz
Setting Range
0.00
–
maximum frequency (P0.12)
Summary of Contents for elmatic ED2000