Group CC: FI/FO Correction
CC.00
FIV measured voltage 1
Default
Factory-corrected
Setting Range
0.500V ~ 4.000V
CC.01
FIV displayed voltage 1
Default
Factory-corrected
Setting Range
0.500V ~ 4.000V
CC.02
FIV measured voltage 2
Default
Factory-corrected
Setting Range
6.000V ~ 9.999V
CC.03
FIV displayed voltage 2
Default
Factory-corrected
Setting Range
6.000V ~ 9.999V
CC.04
FIC measured voltage 1
Default
Factory-corrected
Setting Range
0.500V ~ 4.000V
CC.05
FIC displayed voltage 1
Default
Factory-corrected
Setting Range
0.500V ~ 4.000V
CC.06
FIC measured voltage 2
Default
Factory-corrected
Setting Range
6.000V ~ 9.999V
CC.07
FIC displayed voltage 2
Default
Factory-corrected
Setting Range
-9.999V ~ 10.000V
These parameters are used to correct the Fl to eliminate the impact of Fl zero offset and gain.
They have been corrected upon delivery. When you resume the factory values, these parameters will be restored to the factory
corrected values. Generally, you need not perform correction in the applications.
Measured voltage indicates the actual output voltage value measured by instruments such as the multimeter. Displayed voltage
indicates the voltage display value sampled by the AC drive. For details, refer to D0.21, D0.22 .During correction, send two voltage
values to each Fl terminal, and save the measured values and displayed values to the function codes CC.00 to CC.07. Then the AC
drive will automatically perform Fl zero offset and gain correction.
CC.12
FOV target voltage 1
Default
Factory-corrected
Setting Range
0.500V ~ 4.000V
CC.13
FOV measured voltage 1
Default
Factory-corrected
Setting Range
0.500V ~ 4.000V
CC.14
FOV target voltage 2
Default
Factory-corrected
Setting Range
6.000V ~ 9.999V
CC.15
FOV measured voltage 2
Default
Factory-corrected
Setting Range
6.000V ~ 9.999V
CC.16
Reserved
CC.17
Reserved
CC.18
Reserved
CC.19
Reserved
These parameters are used to correct the FOV.
They have been corrected upon delivery. When you resume the factory values, these parameters will be restored to the factory-
corrected values. You need not perform correction in the applications.
Target voltage indicates the theoretical output voltage of the AC drive. Measured voltage indicates the actual output voltage value
measured by instruments such as the multimeter.
Group D0: Monitoring Parameters
Group D0 is used to monitor the AC drive's running state. You can view the parameter values by using operation panel, convenient
for on-site commissioning, or from the host computer by means of communication .
D0.00 to D0.31 are the monitoring parameters in the running and stopping state defined by P7.03 and P7.04.
For more details, see Table Parameters of Group D0: