P7.10
reserved
Default
P7.11
Software version
Default
Setting Range
Software version of control board
P7.12
Number of decimal
places for load speed display
Default
0
Setting Range
0
0 decimal place
1
1 decimal place
2
2 decimal places
3
3 decimal places
P7.12 is used to set the number of decimal places for load speed display. The following gives an example to explain how to calculate
the load speed:
Assume that P7.06 (Load speed display coefficient) is 2.000 and P7.12 is 2 (2 decimal places). When the running frequency of the
AC drive is 40.00 Hz, the load speed is 40.00 x 2.000 = 80.00 (display of2 decimal places).
If the AC
drive is in the stop state, the load speed is the speed corresponding to the set frequency, namely, •set load speed". If
the set frequency is 50.00 Hz, the load speed in the stop state is 50.00 x 2.000 = 100.00 (display of 2 decimal places).
P7.13
Accumulative power-on time
Default
0h
Setting Range
0h~65535h
It is used to display the accumulative power consumption of the AC drive until now.
Group P8: Auxiliary Functions
P8.00
JOG running frequency
Default
2.00Hz
Setting Range
0.00Hz ~ maximum frequency
P8.01
JOG acceleration time
Default
20.0s
Setting Range
0.0s-6500.0s
P8.02
JOG deceleration time
Default
20.0s
Setting Range
0.0s-6500.0s
These parameters are used to define the set frequency and acceleration/deceleration time of the AC drive when jogging. The
startup mode is "Direct start" (P1.00 = 0) and the stop mode is "Decelerate to stop" (P1.10 = 0) during jogging.
P8.03
Acceleration time 2
Default
Model dependent
Setting Range
0.0s ~ 6500.0s
P8.04
Deceleration time 2
Default
Model dependent
Setting Range
0.0s ~ 6500.0s
P8.05
Acceleration time 3
Default
Model dependent
Setting Range
0.0s ~ 6500.0s
P8.06
Deceleration time 3
Default
Model dependent
Setting Range
0.0s ~ 6500.0s
P8.07
Acceleration time 4
Default
Model dependent
Setting Range
0.0s ~ 6500.0s
P8.08
Deceleration lime 4
Default
Model dependent
Setting Range
0.0s ~ 6500.0s
The ED2000 provides a total of four groups of acceleration/ deceleration time, that is, the preceding three groups and the group
defined by P0.08 and P0.09. Definitions of four groups are completely the same. You can switch over between the four groups of
acceleration/deceleration time through different state combinations of S terminals. For more details, see the descriptions of P5.01
to P5.05.
P8.09
Jump frequency 1
Default
0.00Hz
Setting Range
0.00Hz- maximum frequency