P2.05: the motor rated speed.
In the process of self-learning, the keyboard will display "study", when the keyboard display END, the motor parameter self-
learnings is end.
Note:
in the process of auto-tuning ,moto
r and load should be released, otherwise, the motor parameters obtained from the auto
tuning may not be correct.
2: the static parameters of the self-learning
Motor static parameters auto-tuning , don't need to release motor with the load, motor parameter auto-tuning , must correct the
input parameters of motor nameplates (P2.01 -
P2.05), since auto tuning will detect the motor stator resistance and rotor
resistance and leakage inductance of the motor. And mutual inductance of the motor and no-load current will not be able to
measure, the user can input the corresponding values according to the motor nameplates.
3.4
Running state
3.4.1 Power-on initialization
In the process of the Inverter's power-on, the system first initializes, LED display for "2000", and seven lights all bright. After the
initialization is complete, the drive is in standby mode.
3.4.2 Standby status
In the stopping or running status, can display a variety of state parameters. By Function Code P7.03 (operating parameters), P7.05
(stop parameter) binary bits , Various definitions can refer to P7.03 and P7.05 function code.
3.4.3 Motor parameters self-learning
Please refer to the detailed description of P2.37 a function code.
3.4.4 Running
In the running state, a total of sixteen can choose whether to display the status parameters are: operating frequency, set
frequency, bus voltage, output voltage, output current, operating speed, output power, output torque, PID setting, PID FIV analog
input voltage, analog input voltage FIC, the number of segments multi-speed, torque setpoint, whether to display the function
code is decided by P7.03 and P7.04 bit (converted into binary) choice, press the key to switch the display order of the selected
parameters, press the JOG key to left in order to switch the display selected parameters.
3.4.5 Failure
ED2000 series offers a variety of fault information, please refer ED2000 series inverter faults and their countermeasures.