Note: Modify the function parameters, all related to the frequency parameters of decimal digits will change, the corresponding
frequency values also produces change, pay special attention in the applications.
P0.23
Retentive of digital setting
frequency upon power
Default
0
Setting Range I
0
No memory
1
Memory
The function of frequency source for digital only effective when setting.
"No memory" refers to the inverter after downtime, digital frequency values revert to P0.10(frequency preset)value, the keyboard
bring
▲
,
▼
button or terminal is UP and DOWN to correct the frequency is reset.
"Memory'' refers to the inverter after downtime , digital set frequency keep set for the last moment of downtime, bring about
keyboard
▲
,
▼
button or terminal is UP and DOWN to correct the frequency of remain valid.
P0.24
Acceleration/Deceleration time base frequency
Default
0
Setting Range
0
Maximum frequency (P0.12)
1
Set frequency
2
100Hz
Acceleration/Deceleration time, refers to the frequency from zero to P0.24 set frequency between the Acceleration/Deceleration
time. When the P024 is selected to 1, deceleration time is associated with a set frequency, if set frequency change frequently, the
acceleration of the motor is variable, pay attention to the application.
P0.25
Base frequency for UP/DOWN modification during
running
Default
0
Setting Range
0
Running frequency
1
Set frequency
This parameter is only valid when frequency source for the digital setting.
Used to determine the bring
▲
,
▼
button or terminal of the keyboard UP/DOWN action, adopt what way set frequency correction,
the target frequency is based on the operating frequency, increase or decrease or based on a set frequency increase or decrease.
Two set of distinction, evident when inverter in the deceleration process, namely, if the operation of the inverter frequency and
setting frequency is not at the same time, the parameter of the different selection difference is very big.
P0.26
Binding command source to frequency source
Default
000
Setting Range
Unit's digit
Binding operation panel command to
frequency source
0
No binding
1
Frequency source by digital setting
2
FIV
3
FIC
4
Reserved
5
Pulse setting {S3)
6
Multi-reference
7
Simple PLC
B
PIO
9
Communication setting
P0.26
Setting Range
Ten's digit
Binding terminal command to frequency source(o-9, same as
unit's digit)
Hundred's digit
Binding communication command to frequency source(0-9, same
as unit's digit)