115
Elmark Automatyka S.A.
ul. Niemcewicza 76, 05-075 Warszawa, tel. (+48) 22 773 79 37; [email protected]; www.elmark.com.pl
NIP: 5252072585; KRS: 0000803828, Sąd Rejonowy dla M-St. Warszawy, XIV Wydział Gosp. KRS; Kapitał Zakładowy 525.000 zł, w pełni opłacony
Function
Code
Parameter
Name
Setting Range
Default
Property
PA.02
PID feedback
source
0:FIV
1:FIC
2:Reserved
3:FIV-FIC
4:PULSE setting(S3) 5:Communication setting 6:FIV+FIC
7:MAX(IFIVI, )FICI)
8:MIN(IFIVI, IFICI)
0
☆
PA.03
PID action
direction
0: Forward action
1: Reverse action
0
☆
PA.04
PID setting
feedback range
0 ~ 65535
1000
☆
PA.05
Proportional gain
Kp1
0.0 ~ 100.0
20.0
☆
PA.06
Integral time Ti1 0.01 ~ 10.00s
2.00s
☆
PA.07
Differential time
Td1
0.000s ~ 10.000s
0.000s
☆
PA.08
Cut-off frequency
of PID reverse
rotation
0.00 ~ maximum frequency
2.00Hz
☆
PA.09 PID deviation limit 0.0% ~ 100.0%
0.0%
☆
PA.10
PID differential
limit
0.00% ~ 100.00%
0.10%
☆
PA.11
PID setting change
time
0.00 ~ 650.00s
0.00s
☆
PA.12
PID feedback
filter time
0.00 ~ 60.00s
0.00s
☆
PA.13
PID output filter
time
0.00 ~ 60.00s
0.00s
☆
PA.14
Reserved
-
-
☆
PA.15
Proportional gain
Kp2
0.0 ~ 100.0
20.0
☆
PA.16
Integral time Ti2 0.01s ~ 10.00s
2.00s
☆
PA.17
Differential time
Td2
0.000s ~ 10.000s
0.000s
☆
PA.18
PID parameter
switchover
condition
0: No switchover
1:Switchover via S
2:Automatic switchover based on deviation
0
☆
PA.19
PID parameter
switchover
deviation 1
0.0% ~ PA.20
20.0%
☆
PA.20
PID parameter
switchover
deviation 2
PA.19 ~ 100.0%
80.0%
☆
PA.21
PID initial value 0.0% ~ 100.0%
0.0%
☆
Summary of Contents for elmatic ED2000