Function
Code
Parameter
Name
Setting Range
Default
Property
C0.00
Speed/torque
control selection
0: Speed control
1: Torque control
0
★
C0.01
Torque setting
source in torque
control
0: Digital setting (C0.03 )
1: FIV
2: FIC
3: reserved
4: PULSE setting
5: Communication setting
6: MIN(FIV,FIC)
7: MAX (FIV,FIC )
0
★
C0.03
Torque digital
setting in
-200.0% ~ 200.0%
150.0%
☆
C0.05
Forward maximum
frequency in
torque control
0.00Hz ~ maximum frequency
50.00Hz
☆
C0.06
Reverse maximum
frequency in
torque control
0.00Hz ~ maximum frequency
50.00Hz
☆
C0.07
Acceleration
time in torque
control
0.00s ~ 650.00s
0.00s
★
C0.08
Deceleration time
in torque
control
0.00s ~ 650.00s
0.00s
☆
Group C1-C4: Reserved
Group C5: Control Optimization Parameters
C5.00
PWM
switchover
frequency upper
limit
0.00Hz ~ 15.00Hz
12.00Hz
☆
C5.01
PWM
modulation mode
0: Asynchronous modulation
1: Synchronous modulation
0
☆
C5.02
Dead zone
compensation
mode selection
0: No compensation
1: Compensation mode 1
2: Compensation mode 2
1
☆
C5.03
Random PWM
depth
0: Random PWM invalid
1-10: PWM canier frequency random depth
0
☆
C5.04 Rapid currant limit
0: Disabled
1: Enabled
1
☆
C5.05
Current
detection
compensation
0 ~ 100
5
☆
C5.06
Undervoltage
threshold
60.0% ~ 140.0%
100.0%
☆
C5.07
SFVC
optimization
mode selection
0: No optimization
1: Optimization mode 1
2: Optimization mode 2
1
☆