background image

 

 

Step

1

Model Identification and  
Mounting 

Connect Motor and  

Line Power 

Step

2

Step

3

Page 1 of 4 

WARNING! Fire Hazard. Only connect ground wiring to 
designated ground terminals. Do not connect the following 
terminals to earth ground.

9. Figures 1 and 2

 show the electrical connections for input 

power and motor terminals.

 Select the proper figure for the 

model being installed 

(Refer to Step 1). 

WITH POWER OFF make the appropriate connections.
Follow good wiring practices and all applicable electric codes. 
Ensure the equipment is grounded properly 
as shown in Figure 1.

                W

WARNING! Hazardous Voltage. After the power is 

OFF, wait at least five minutes until the charge indicator 
extinguishes completely before touching any wiring, circuit 
boards or components. 

Verify the drive is properly sized for single phase input power. The drive 
input supply voltage must be equal to or greater than motor rated voltage 
for best performance.

*

U/T1 V/T2 W/T3

3Ø Induction 

motor

1Ø Input Power

Connect 
frame to 

ground

Input
Protection
(Fuse or C.B.)

To change direction 
of motor rotation, 
swap any 

two of the 

three motor leads 
(Refer to Step 2)

L1 L2

Figure 1:

 Input Power and Output Motor Electrical 

Connections for Single Phase Input iQpumpMicro 

SINGLE PHASE 

INPUT 

iQpump Micro

Connect to chassis 
ground

R/L1 S/L2

U/T1 V/T2 W/T3

3Ø Induction 

motor

3Ø Input Power

L1 L2 L3

Figure 2: 

Input Power and Output Motor Electrical 

Connections for Three Phase Input iQpump Micro 

R/L1 S/L2 T/L3

THREE PHASE 

INPUT 

iQpump Micro

-

+1

+2

(S/L2)

(R/L1)

(U/T1) (V/T2) (W/T3)

(U/T1) (V/T2) (W/T3)

To change direction 
of motor rotation, 
swap any 

two of the 

three motor leads 
(Refer to Step 2)

Connect 
frame to 

ground

Input
Protection
(Fuse or C.B.)

Connect to chassis 
ground

(R/L1) (S/L2) (T/L3)

B1

B2

1. Verify the correct drive model and ratings.
2. Locate the drive nameplate and your order information.
3. Verify the drive MODEL No. matches the line item(s) on 
your order, to confirm receipt of the correct model. 
4. Locate the nameplate of motor that will be connected to the 
drive.
5. Confirm the motor nameplate Amperage, Voltage, and 
Frequency (Hz) are within the O

Output specifications shown on 

the drive nameplate. 

·

Verify main  input power source is adequate by reviewing 
the Input specifications drive nameplate. 

 

Mechanical Installation

·

Follow the above procedure for each iQpumpMicro and 
motor combination.

7. Adhere to environmental specifications to avoid damage to 
the equipment and to maintain safety. For NEMA 4 model 
environmental conditions, refer to instructions supplied with 
the product.

Removing and Attaching the Terminal Cover

 6. Mechanical installation and mounting footprint vary by 
drive model.  Refer to the iQpump Micro User Manual 
No.TOEPYAIQPM03  

Section 2 Mechanical Installation,

 for 

mechanical installation details. Refer to the proper 
clearances required for adequate ventilation in systems 
containing multiple drives.  

8. 

Improper removal of the the drive’s protective covers and 

conduit bracket (NEMA 1) can cause damage to the drive. 
Adhere to iQpump User Manual, Section 3, 

Protective 

Covers 

to avoid drive damage. 

 

NEMA 1

Installation Environment (IP20/NEMA TYPE 1)

Environment 

Conditions 

Installation Area 

Indoors 

Ambient Temperature  + 14 to 104 °F (-10 to +  40 °C) NEMA Type 1 Enclosure 

Humidity 

95% RH or less and free of condensation 

Storage Temperature  -20 to + 60 °C 

 
Surrounding Area 

Install the drive in an area free from: 

 

oil mist and dust 

 

metal shavings, oil, water, or other foreign materials 

 

radioactive materials 

 

combustible materials (e.g., wood) 

 

harmful gases and liquids 

 

excessive vibration 

 

chlorides 

 

direct sunlight. 

Altitude 

1000 meters  or lower 

Vibration 

10 to 20 Hz at 9.8 m/s2 
20 to 55 Hz at 5.9 m/s2   

Orientation 

Install the drive vertically to maintain maximum cooling 
effects. 

iQpump Micro control and transducer feedback signal wiring connections. 
WARNING! Hazardous Voltage. Contact may cause electric shock or burn. Turn-off and lock-out system and facility power before servicing 
Remove the terminal cover to gain access to the control terminals. (Step 1.)

10. SELECT START / STOP CONTROL METHOD

b1-02

NOTE: Refer to the iQpump Micro User Manual,
(Document No. TOEPYAIQPM03)  to program the iQpump Micro drive 
for network communication control.  

11. TRANSDUCER  FEEDBACK SIGNAL WIRING       [REFER TO PAGE 7 OF 12 FOR 24 V POWER SUPPLY INSTALLATION]

Initialize the iQpump Micro 
Set parameter A1-03 = 3330 
to use 3-Wire Control  
Refer to:
Quick Start Guide 
TOEPYAIQPM02

The iQpump Micro is D

DEFAULT SETUP TO START/STOP FROM THE KEYPAD (digital operator). If this is the preferred start/stop method then 

continue to the feedback signal connection section.  Please refer to the wiring diagram below to start/stop the iQpump Micro using an external switch 
or contact. 

S3

S5 S6 S7 HC SC H1 RP

S2

S4

S1

Forward

Run

S3

S5 S6 S7 HC SC H1 RP

S2

S4

S1

Start

Switch

Stop 

Switch

Normally 

Open

Normally 

Closed

Use for maintained contacts

iQpump Micro Terminals TB1-1

iQpump Micro Terminals TB1-1

 3-Wire Control

 2-Wire Control

Wiring Diagrams

3-Wire, 0-10V Transducer

2-Wire, 4-20mA Transducer

Set DIP switch S1 to V position 
for use with 0 

 10V Transducer

See far right 

NOTE: Transducer wire colors and 
numbering may vary depending on
feedback device used,
consult feedback device manual.

NOTE: Transducer wire colors and 
numbering may vary depending on
feedback device used,
consult feedback device manual.

Selecting Start/Stop and Speed Method 

WARNING! 

Read and understand 
users manual before 
using this equipment

.

This Quick Start 
Procedure will help 
you configure the 
iQpump Micro (drive) 
for test run operation 
and basic set-up for 
simplex pump 
application.

Refer to the User 
Manual No. 
TOEPYAIQPM03, 
for detailed 
instructions and to 
configure the drive 
for each specific 
installation site.  

Safety Symbols in 
this Document

   W

WARNING! 

Hazardous Voltage. 
Contact may cause 
electric shock or burn. 
Turn-off and lock-out 
system and facility 
power before servicing.

WARNING! 

Stay Clear- Equipment 
starts automatically. 
Clear all personnel 
from equipment, install 
shields or guards, 
locate and verify 
emergency SHUT-OFF 
is functional. Failure to 
comply may result in 
serious injury to 
personnel.

   WARNING! 

Improper Operation 
Sequence. DO NOT 
RUN THE MOTOR. 
Failure to comply may 
result in serious injury 
to personnel.

    WARNING! 

Do not operate 
equipment with covers 
or guards removed.
Install or replace cover 
and/or guards before 
operation. Failure to 
comply may result in 
serious injury to 
personnel.

R

R

R d

d

St

Yaskawa America, Inc., 2121 Norman Drive South, Waukegan, IL 60085, (800) YASKAWA (927-5292)     Fax (847) 887-7310, [email protected], www.yaskawa.com, Document Number: TOEPYAIQPM01 

11/2014  © Yaskawa America, Inc.

 

 

Page 1 of 12 

iQpump Micro AC Drive 
Simplex Quick Start Procedure  

Summary of Contents for iQpump Micro

Page 1: ...RH or less and free of condensation Storage Temperature 20 to 60 C Surrounding Area Install the drive in an area free from oil mist and dust metal shavings oil water or other foreign materials radioac...

Page 2: ...onitor signals Press simultaneously shows the monitor menu Use to select monitor Press to access monitor menu LED Digital Operator Standard LCD Digital Operator Optional Motor Current Increase Decreas...

Page 3: ...p Mode is set to 3 MEMOBUS network this function is active only on the first drive in the network Programming the Start Level as an Absolute Value Start Draw Down Level must be programmed to a positiv...

Page 4: ...tal operator THRUST BEARING SUBMERSIBLE MOTORS The factory recommends using the T Thrust Bearing function to prevent excess motor wear when u using a submersible motor in combination with the iQpump M...

Page 5: ...hould read as in Figure 3 No alarm active Auto Mode Off Hand Mode Off NOTE If the motor direction is not correct de energize the iQpump Micro and follow instructions below Press to access HAND Speed U...

Page 6: ...iQpump Micro User Manual Document No TOEPYAIQPM03 for additional information c Re enable the Anti No Flow function by setting P2 23 to 0 40 and continue to Step 1 to verify no flow sleep operation onc...

Page 7: ...7 5292 Fax 847 887 7310 DrivesHelpDesk yaskawa com www yaskawa com Document Number TOEPYAIQPM01 11 2014 Yaskawa America Inc Step 11 24 V Power Supply Installation Page 7 of 12 iQpump Micro AC Drive Si...

Page 8: ...2 Fax 847 887 7310 DrivesHelpDesk yaskawa com www yaskawa com Document Number TOEPYAIQPM01 11 2014 Yaskawa America Inc Page 8 of 12 iQpump Micro AC Drive Simplex Quick Start Procedure Step 11 24 V Pow...

Page 9: ...2 Fax 847 887 7310 DrivesHelpDesk yaskawa com www yaskawa com Document Number TOEPYAIQPM01 11 2014 Yaskawa America Inc Page 9 of 12 iQpump Micro AC Drive Simplex Quick Start Procedure Step 11 24 V Pow...

Page 10: ...Fax 847 887 7310 DrivesHelpDesk yaskawa com www yaskawa com Document Number TOEPYAIQPM01 11 2014 Yaskawa America Inc Page 10 of 12 iQpump Micro AC Drive Simplex Quick Start Procedure Step 11 24 V Pow...

Page 11: ...Fax 847 887 7310 DrivesHelpDesk yaskawa com www yaskawa com Document Number TOEPYAIQPM01 11 2014 Yaskawa America Inc Page 11 of 12 iQpump Micro AC Drive Simplex Quick Start Procedure Step 11 24 V Pow...

Page 12: ...Fax 847 887 7310 DrivesHelpDesk yaskawa com www yaskawa com Document Number TOEPYAIQPM01 11 2014 Yaskawa America Inc Page 12 of 12 iQpump Micro AC Drive Simplex Quick Start Procedure Step 11 24 V Pow...

Reviews: