iQpump Micro Quick Setup Parameter Overview (Simplex) 

 

Yaskawa America, Inc., 2121 Norman Drive South, Waukegan, IL 60085, (800) YASKAWA (927-5292)     Fax (847) 887-7310, [email protected], www.yaskawa.com, Document Number: TOEPYAIQPM01 

11/2014  © Yaskawa America, Inc.

 

Page 3 of 12 

iQpump Micro AC Drive 
Simplex Quick Start Procedure  

Parameter

 

Value

 

Description

 

Reference

 

A1-06 

Dependent 

on 

Initialization 

Mode 

Application Preset 

Displays selected applications, see Step 5. 

Comment:  
Read-only cannot be modified. Factory set to (0: Pressure control) 

E2-01 

Drive Size  

Dependent 

Motor Rated Current  Set to the motor nameplate full load amps. 

Comment:  
For submersible motors use service  factor amps (SFA). 

E2-04 

Number of Motor 
Poles 

Sets the number of motor poles. 

Number of motor poles is used to show the correct motor RPM on the display 

Enter ’4’ for an 1800 RPM motor and ‘2’ for a 3600 RPM motor.

 

Comment:  
Confirm number of poles: 2 Pole Motor = 3600 RPM,  4 Pole Motor = 1800 RPM, 6 Pole Motor = 1200 RPM, 8 Pole Motor = 900 RPM 

P1-03 145.0 

Feedback Device  
Scaling 

Sets the scaling of feedback device in user-set units. 

System Scaling:  Enter feedback device maximum: 

Example: Enter 200 for pressure transducer with a maximum of 200 PSI at 20mA. 

Comment:  
Confirm feedback device scaling. 

(See Illustration 1) 

Q1-01 

0.0 

PID Controller Set-
point 1 

Sets the PID Setpoint when b1-01 is set to 0. 

Comment: 

Set to system pressure

 

Parameter

 

Value

 

Description

 

Reference

 

P1-04 

0.0 PSI 

Start / Drawn  Down  
Level 

The system starts when the feedback level drops below the start level for the time set in P1-05 

(default 1 sec). This level also specifies the wakeup level when the drive is in Sleep Mode. When 

this parameter is set to a negative value, the feedback level must drop that amount below the 

setpoint. Setting this parameter to 0.0 disables the function. When P1-01, Pump Mode, is set to 

3 (MEMOBUS network), this function is active only on the first drive in the network. 

 

Programming the Start Level as an Absolute  

Value. 

Start / Draw Down Level must be  programmed to a positive value for the Start / Draw 

Down Level to be an absolute value.   

Example: Start / Draw Down Level P1-04 set to 

50 PSI 

and delay time P1-05 set to 

5 sec.  

Result: 

Pump system will start when the pressure drops below 50 PSI for 5 sec.  

 

Programming the Start Level as a Delta Level from the System Setpoint

 

Start / Draw Down Level must be programmed to a negative value for the Start Level to be a 

delta value from the setpoint.  

Example: Start / Draw Down Level P1-04 set to 

10 PSI 

with a system setpoint of 

50 PSI 

and de-

lay time P1-05 set to 

5 sec

.  

Result: 

Pump system will start when the pressure drops below 40 PSI (50 - 10) for 5 sec.  

Comment:  
It is mandatory to program the Start / Draw Down Level in order to use the sleep function. (

See Illustration 2 and 3 below) 

P1-06 

40.0 Hz 

Minimum Pump  
Speed 

Minimum speed (Hz) for pump motor operation. 

Example:

 Base pump motor speed is 3600 RPM, minimum speed is 2400 RPM.  

Set minimum pump frequency to 40.0 Hz. (2400 ÷ 3600 x 60 Hz = 40 Hz)

 

Comment:  
Minimum pump frequency should be set to the value at which the pump enters a no-flow condition. 

P4-10 

Disabled 

AUTO Mode Opera-
tor Run Power Down 
Storage 

Stores the run status in the AUTO mode when operating from digital operator (b1-02=0). 
0: Disabled 
1: Enabled 
             

          WARNING! Sudden Movement Hazard. 

If the drive is powered down while running, it will     

          automatically initiate an internal Run command upon power-up. 

Comment: 
Recommended for use when the Start/Stop command is from the digital operator 

(See Step 9) 

P5-04

Enabled 

HAND Key Function 
Selection 

Enables or disables the HAND key on the digital operator. 
0: Disabled
1: Enabled 

Comment:  
HAND key on digital operator. 

(See Step 10) 

iQpump Micro Quick Setup Parameter Overview (Simplex continued) 

Use                            

to change the sign.

Use                            

to change the sign.

LED Digital Operator

LCD Digital Operator

      

 

 

Illustration 2

 

Illustration 3

 

Step

6

Summary of Contents for iQpump Micro

Page 1: ...RH or less and free of condensation Storage Temperature 20 to 60 C Surrounding Area Install the drive in an area free from oil mist and dust metal shavings oil water or other foreign materials radioac...

Page 2: ...onitor signals Press simultaneously shows the monitor menu Use to select monitor Press to access monitor menu LED Digital Operator Standard LCD Digital Operator Optional Motor Current Increase Decreas...

Page 3: ...p Mode is set to 3 MEMOBUS network this function is active only on the first drive in the network Programming the Start Level as an Absolute Value Start Draw Down Level must be programmed to a positiv...

Page 4: ...tal operator THRUST BEARING SUBMERSIBLE MOTORS The factory recommends using the T Thrust Bearing function to prevent excess motor wear when u using a submersible motor in combination with the iQpump M...

Page 5: ...hould read as in Figure 3 No alarm active Auto Mode Off Hand Mode Off NOTE If the motor direction is not correct de energize the iQpump Micro and follow instructions below Press to access HAND Speed U...

Page 6: ...iQpump Micro User Manual Document No TOEPYAIQPM03 for additional information c Re enable the Anti No Flow function by setting P2 23 to 0 40 and continue to Step 1 to verify no flow sleep operation onc...

Page 7: ...7 5292 Fax 847 887 7310 DrivesHelpDesk yaskawa com www yaskawa com Document Number TOEPYAIQPM01 11 2014 Yaskawa America Inc Step 11 24 V Power Supply Installation Page 7 of 12 iQpump Micro AC Drive Si...

Page 8: ...2 Fax 847 887 7310 DrivesHelpDesk yaskawa com www yaskawa com Document Number TOEPYAIQPM01 11 2014 Yaskawa America Inc Page 8 of 12 iQpump Micro AC Drive Simplex Quick Start Procedure Step 11 24 V Pow...

Page 9: ...2 Fax 847 887 7310 DrivesHelpDesk yaskawa com www yaskawa com Document Number TOEPYAIQPM01 11 2014 Yaskawa America Inc Page 9 of 12 iQpump Micro AC Drive Simplex Quick Start Procedure Step 11 24 V Pow...

Page 10: ...Fax 847 887 7310 DrivesHelpDesk yaskawa com www yaskawa com Document Number TOEPYAIQPM01 11 2014 Yaskawa America Inc Page 10 of 12 iQpump Micro AC Drive Simplex Quick Start Procedure Step 11 24 V Pow...

Page 11: ...Fax 847 887 7310 DrivesHelpDesk yaskawa com www yaskawa com Document Number TOEPYAIQPM01 11 2014 Yaskawa America Inc Page 11 of 12 iQpump Micro AC Drive Simplex Quick Start Procedure Step 11 24 V Pow...

Page 12: ...Fax 847 887 7310 DrivesHelpDesk yaskawa com www yaskawa com Document Number TOEPYAIQPM01 11 2014 Yaskawa America Inc Page 12 of 12 iQpump Micro AC Drive Simplex Quick Start Procedure Step 11 24 V Pow...

Reviews: