Step

8

Verify Pump Rotation and Transducer Feedback Signal 

Page 5 of 12 

iQpumpMicro AC Drive 
Simplex Quick Start Procedure  

15. Motor Rotation Test

14. This step checks the motor for proper direction and operation. This test is performed solely from the digital operator.

 

Apply power to the iQpump Micro after electrical connections are terminated and protective covers are installed. 
At this point, D

DO NOT RUN THE MOTOR,  The digital operator should display as shown in 

Figure 3

.

Figure 3: Digital Operator

Refer to

 Figure 1 or 2,

 swap any ttwo 

of the tthree output leads to the motor 
(U/T1, V/T2 and W/T3). Repeat S

Step 8 

and recheck motor direction after the 
wiring change.    

WARNING! Hazardous Voltage. Contact may cause electric shock or burn. Turn-off and lock-out system and facility power before servicing. 
After the power has been turned OFF, wait at least five minutes until the charge indicator extinguishes completely before touching any wiring, 
circuit boards or components.

Verify the transducer feedback signal level on the digital operator display matches a mechanical pressure gauge.

FEEDBACK SIGNAL LEVEL

Refer to parameter P1-02 
and P1-03, if the feedback 
device scaling or system 
units are incorrect. 

Press

and the HAND

LED  should be 

ON

The motor should  be operating in the correct direction of pump.

Press

on the digital operator; the display should read

on the digital operator; the display should read as in Figure 3.

Auto Mode Off

Press               to access Hand Speed. Use                                to change 

HAND Speed value. Press               to save value.

No alarm active

Hand Mode Off

Digital operator 

turned off.

Figure 3: Digital Operator

Digital operator 

turned off.

FEEDBACK SIGNAL LEVEL

Press

and the HAND

LED  should be 

ON

The motor should now be operating at in the correct direction of pump.

Press

on the Digital Operator; the display should read

on the Digital Operator; the display should read as in Figure 3.

No alarm active

Auto Mode Off

Hand Mode Off

NOTE: If the motor direction is not correct, de-energize the iQpump Micro and follow instructions below.

Press               to access HAND Speed. Use                                     to change 

HAND Speed value. Press               to save value.

LED Digital Operator (Standard)

LCD Digital Operator (Optional)

16. Feedback Signal Check

Refer to

 Figure 1 or 2,

 swap any 

two of the tthree output leads to 
the motor (U/T1, V/T2 and W/T3). 
Repeat S

Step 8 and recheck motor 

direction after the wiring change.    

From HOME screen, 

press               to access “

FEEdb

” screen

FEEdb

” will display for 

2 seconds, then automatically change to display the 

feedback signal level.

17. AUTO MODE

Press the A

AUTO button to place the iQpump Micro into AUTO mode. 

The AUTO mode will start and stop based on the Run Source Selection setting parameter b1-02. (Refer to Step 3) The 
Reference Source Selection parameter b1-01 setting configures the AUTO mode reference source.

Press

to access or modify the system setpoint entered in parameter Q1-01 within the  

18. SET SYSTEM SETPOINT

The iQpump Micro starts in AUTO Mode when the feedback signal level falls below the level programmed in parameter 
P1-04 for the specified time in P1-05.

Use 

to select the digit and

Next press 

Press the A

AUTO button to 

start the iQpump Micro.

Start Pump System

Start

Delay

145 PSI

Start / Draw Down 
Level P1-04

System Setpoint
(Example 80 PSI)

Feedback signal from 

pressure transducer 

(4 

 20 mA)

0

Pressure

Start Level Delay (P1-05)

(Example 5.0 sec.)

WAIT

to store setpoint.

Refer to Page 3, parameter P1-04  for details on the Start Level Function.

iQpump Micro Quick Setup Menu.

Example: 80 PSI

Figure 4: Digital Operator

LED is blinking 

when AUTO mode 

is active but AUTO 

Run Command is 

not active.

The iQpump Micro is operated in AUTO mode by performing the following tasks:
·

Program all parameters

·

Verify motor rotation direction

·

Auto Mode: Select the R

Reference source setting in parameter b1-01

·

Auto Mode: Select the R

Run source setting in parameter b1-02 (Refer to Step 3)

Next, press 

to return to the main menu (LCD Digital Operator)

LED Digital Operator (Standard)

LCD Digital Operator (Optional)

LED Digital Operator (Standard)

LCD Digital Operator (Optional)

SETPOINT

PRESS AUTO BUTTON

PRESS TO TURN OFF

Step

9

Auto Mode Operation 

Summary of Contents for iQpump Micro

Page 1: ...RH or less and free of condensation Storage Temperature 20 to 60 C Surrounding Area Install the drive in an area free from oil mist and dust metal shavings oil water or other foreign materials radioac...

Page 2: ...onitor signals Press simultaneously shows the monitor menu Use to select monitor Press to access monitor menu LED Digital Operator Standard LCD Digital Operator Optional Motor Current Increase Decreas...

Page 3: ...p Mode is set to 3 MEMOBUS network this function is active only on the first drive in the network Programming the Start Level as an Absolute Value Start Draw Down Level must be programmed to a positiv...

Page 4: ...tal operator THRUST BEARING SUBMERSIBLE MOTORS The factory recommends using the T Thrust Bearing function to prevent excess motor wear when u using a submersible motor in combination with the iQpump M...

Page 5: ...hould read as in Figure 3 No alarm active Auto Mode Off Hand Mode Off NOTE If the motor direction is not correct de energize the iQpump Micro and follow instructions below Press to access HAND Speed U...

Page 6: ...iQpump Micro User Manual Document No TOEPYAIQPM03 for additional information c Re enable the Anti No Flow function by setting P2 23 to 0 40 and continue to Step 1 to verify no flow sleep operation onc...

Page 7: ...7 5292 Fax 847 887 7310 DrivesHelpDesk yaskawa com www yaskawa com Document Number TOEPYAIQPM01 11 2014 Yaskawa America Inc Step 11 24 V Power Supply Installation Page 7 of 12 iQpump Micro AC Drive Si...

Page 8: ...2 Fax 847 887 7310 DrivesHelpDesk yaskawa com www yaskawa com Document Number TOEPYAIQPM01 11 2014 Yaskawa America Inc Page 8 of 12 iQpump Micro AC Drive Simplex Quick Start Procedure Step 11 24 V Pow...

Page 9: ...2 Fax 847 887 7310 DrivesHelpDesk yaskawa com www yaskawa com Document Number TOEPYAIQPM01 11 2014 Yaskawa America Inc Page 9 of 12 iQpump Micro AC Drive Simplex Quick Start Procedure Step 11 24 V Pow...

Page 10: ...Fax 847 887 7310 DrivesHelpDesk yaskawa com www yaskawa com Document Number TOEPYAIQPM01 11 2014 Yaskawa America Inc Page 10 of 12 iQpump Micro AC Drive Simplex Quick Start Procedure Step 11 24 V Pow...

Page 11: ...Fax 847 887 7310 DrivesHelpDesk yaskawa com www yaskawa com Document Number TOEPYAIQPM01 11 2014 Yaskawa America Inc Page 11 of 12 iQpump Micro AC Drive Simplex Quick Start Procedure Step 11 24 V Pow...

Page 12: ...Fax 847 887 7310 DrivesHelpDesk yaskawa com www yaskawa com Document Number TOEPYAIQPM01 11 2014 Yaskawa America Inc Page 12 of 12 iQpump Micro AC Drive Simplex Quick Start Procedure Step 11 24 V Pow...

Reviews: