Chapter 7 Parameters
ASDA-B2
7-12
Revision May, 2018
7.3 Parameter
Description
P0-xx Monitor Parameters
P0-00
★
VER Firmware Version
Address: 0000H
0001H
Operation
Interface:
Panel/Software
Communication
Related Section: N/A
Default:
Factory setting
Control
Mode:
ALL
Unit: -
Range: -
Data Size: 16-bit
Format: Decimal
Settings: This parameter only shows the firmware version of the servo
drive.
P0-01
■
ALE
Alarm Code Display of Drive
(Seven-segment Display)
Address: 0002H
0003H
Operation
Interface:
Panel/Software
Communication
Related Section:
11.1, 11.2, 11.3
Default:
-
Control
Mode:
ALL
Unit: -
Range: 0 ~ 0
It only can be set to 0 to clear the alarm
(Same as DI.ARST).
Data Size: 16-bit
Format: BCD
Settings: Hexadecimal format: displays the alarm code
0x0000: alarm clear (same as DI:ARST).
0x0000 ~ 0xFFFF: displays the alarm code (not writable).
For the list of alarms, please refer to Section 9.1 Alarm of Servo
Drive.
Alarm of Servo Drive
001: Over current
002: Over voltage
003: Under voltage (In default setting, the alarm occurs only
when the voltage is not enough in Servo ON status; In Servo
ON status, when it applies to power R, S, T, the alarm still
will not be cleared. Please refer to P2-66.)
004: Motor combination error (The drive corresponds to the
wrong motor)
005: Regeneration error