Chapter 3 Wiring
ASDA-B2
3-2
Revision May, 2018
NOTE
Installation notes:
1. Check if the power and wiring among R, S, T and L1c, L2c are correct.
2. Please check if the output terminal U, V, W of the servo motor is correctly
wired. The incorrect wiring may disable the operation of the motor or cause
malfunction.
3. When applying to the external regenerative resistor, the contact between
P
and D should be opened and the external regenerative resistor should
connect to terminal P
and C. When applying to the internal regenerative
resistor, the contact between P
and D should be closed and the contact
between P
and C should be opened.
4. When an alarm occurs or the system is in emergency stop status, use
ALARM or WARN to output and disconnect the power of magnetic
contactor in order to disconnect the power of servo drive.
3.1.2 Servo Drive Connectors and Terminals
Terminal
Signal
Name
Description
L1c, L2c
Control circuit
terminal
Used to connect single-phase AC control circuit power.
(Control circuit uses the same voltage as the main circuit.)
R, S, T
Main circuit
terminal
Used to connect three-phase AC main circuit power
depending on connecting servo drive model.
U, V, W,
FG (
)
Servo motor
output
Used to connect servo motor
Terminal
Symbol
Wire
Color
Description
U Red
Connecting to three-phase motor
main circuit cable.
V White
W Black
FG(
)
Green
Connecting to ground terminal
(
) of the servo drive.
P
, D, C,
Regenerative
resistor terminal
or braking unit
Internal
resistor
Ensure the circuit is closed between P
and D, and the circuit is open between P
and C.
External
resistor
Connect regenerative resistor to P
and C,
and ensure an open circuit between P
and D.
External
braking
unit
Connect braking unit to P
and
, and
ensure an open circuit between P
and D,
and P
and C.
(N terminal is built in L1c, L2c,
, and R, S,
T.)
P
:
Connecting to (+) terminal of V_BUS
voltage.
: Connecting to (-) terminal of V_BUS
voltage.