ASDA-B2
Chapter 7 Parameters
Revision May, 2018
7-93
P4-17
COF3
Current Detector (W1 phase) Offset
Adjustment
Address: 0422H
0423H
Operation
Interface:
Panel / Software
Communication
Related Section: N/A
Default:
Factory setting
Control
Mode:
ALL
Unit: N/A
Range: 0 ~ 32767
Data Size: 16-bit
Format: Decimal
Settings: Manually adjust the hardware offset. The adjustment function
needs to be enabled by the setting of parameter P2-08. It is not
suggested to adjust the auxiliary adjustment. This parameter
cannot be reset.
P4-18
COF4
Current Detector (W2 phase) Offset
Adjustment
Address: 0424H
0425H
Operation
Interface:
Panel / Software
Communication
Related Section: N/A
Default:
Factory setting
Control
Mode:
ALL
Unit: N/A
Range: 0 ~ 32767
Data Size: 16-bit
Format: Decimal
Settings: Manually adjust the hardware offset. The adjustment function
needs to be enabled by the setting of parameter P2-08. It is not
suggested to adjust the auxiliary adjustment. This parameter
cannot be reset.
P4-19
TIGB
IGBT NTC Adjustment Detection Level
(cannot reset)
Address: 0426H
0427H
Operation
Interface:
Panel / Software
Communication
Related Section: N/A
Default:
Factory setting
Control
Mode:
ALL
Unit: N/A
Range: 1 ~ 3
Data Size: 16-bit
Format: Decimal
Settings: Please cool down the drive to 25 Celsius degree when adjusting.