Universal Data Manager
Anhang
87
Options
None, One (X.Y), Two (X.YY), Three (X.YYY), Four (X.YYYY), Five (X.YYYYY)
Factory setting
One (X.Y)
Lower frequency
Navigation
Expert → Inputs → Universal inputs → Universal input x → Lower frequency
Direct access code: 220018-0xx
Examples: Universal input 1: 220018-000; Universal input 12: 220018-011
Description
Configure the lower frequency that corresponds to the start of the measuring range.
Only visible if signal = frequency input
User entry
Number (max. 8 digits), minimum: 0
Factory setting
5
Range start
Navigation
Expert → Inputs → Universal inputs → Universal input x → Range start
Direct access code: 220006-0xx
Examples: Universal input 1: 220006-000; Universal input 12: 220006-011
Description
Transmitters convert the physical measured variable to standardized signals. Enter the
start of the measuring range here.
• The start and end of the measuring range may not be identical.
• The start of the measuring range can also be larger than the end (e.g. for deep
wells).
• The parameter can be defined independently of the number of decimal places
configured for the measured value as these are only taken into consideration for the
display.
User entry
Number (max. 8 digits)
Factory setting
Depends on the input signal selected
Upper frequency
Navigation
Expert → Inputs → Universal inputs → Universal input x → Upper frequency
Direct access code: 220019-0xx
Examples: Universal input 1: 220019-000; Universal input 12: 220019-011
Description
Configure the upper frequency that corresponds to the end of the measuring range.
Only visible if signal = frequency input
User entry
Number (max. 8 digits)