ACS-CONTROL-SYSTEM GmbH
l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
92
Anhang
Universal Data Manager
92
Navigation
Expert → Inputs → Universal inputs → Universal input x → Measured value
correction → Target value
Direct access code: 220052-0xx
Examples: Universal input 1: 220052-000; Universal input 12: 220052-011
Description
Enter the lower setpoint here (e.g. measuring range 0°C to 100°C: 0°C).
Only visible if signal = current or voltage
User entry
Number (max. 8 digits)
Factory setting
0
Actual value
Navigation
Expert → Inputs → Universal inputs → Universal input x → Measured value
correction → Actual value
Direct access code: 220053-0xx
Examples: Universal input 1: 220053-000; Universal input 12: 220053-011
Description
Enter the lower value actually measured here (e.g. measuring range 0°C to 100°C:
measured value 0.5°C).
Only visible if signal = current or voltage
User entry
Number (max. 8 digits)
Factory setting
0
Meas. range end
Target value
Navigation
Expert → Inputs → Universal inputs → Universal input x → Measured value
correction → Target value
Direct access code: 220055-0xx
Examples: Universal input 1: 220055-000; Universal input 12: 220055-011
Description
Enter the upper setpoint here (e.g. measuring range 0°C to 100°C: 100°C).
Only visible if signal = current or voltage
User entry
Number (max. 8 digits)
Factory setting
100
Actual value