Universal Data Manager
Anhang
105
Options
Closing, Opening
Factory setting
Closing
Identifier
Navigation
Expert → Outputs → Relay x → Identifier
Direct access code: 330001-00x
Examples: Relay 1:330001-000; Relay 6: 330001-005
Description
Presettable relay identifier.
User entry
Text (max. 16 characters)
Factory setting
Relay x
16.1.4 "Communication" submenu
Set-up required if you are using the USB, RS232, RS485 or Ethernet interface of the unit
(PC operation, serial data read-out, modem operation, etc.).
The various interfaces can be operated in parallel.
Timeout
Navigation
Expert → Communication → Timeout
Direct access code: 150200-000
Description
The device monitors whether measured values are read out via the OPC server or the
fieldbus (e.g. Modbus Slave). A relay can be switched if no more values are read out over
the set timeout period. Timeout is modifiable between 1 and 99 seconds. 0 seconds means
that the functionality is inactivated.
User entry
0 to 99
Factory setting
0
Switches
Navigation
Expert → Communication → Switches
Direct access code: 150201-000
Description
After the given timeout the dedicated relay/OC is active while no readout of actual
measured values are in process.