Undetectable errors: wherever possible, errors in the formula are reported immediately
during input. However, given the possible complexity of the formula entered (e.g. nested
formulas) it is not possible to detect every error.
"Totalization" submenu
Navigation
Expert → Application → Maths → Maths x → Totalization
Description
Settings only needed if the calculated value - e.g. for quantity calculation - should be
integrated. Analysis time frames, see "Signal analysis".
Totalization
Navigation
Expert → Application → Maths → Maths x → Totalization → Totalization
Direct access code: 400050-00x
Examples: Maths 1: 400050-000; Maths 4: 400050-003
Description
By totalizing the analog signal (e.g. flow rate in m³/h) quantities (in m³) can be calculated.
Options
No, Yes
Factory setting
No
Totalization base
Navigation
Expert → Application → Maths → Maths x → Totalization → Totalization base
Direct access code: 400051-00x
Examples: Maths 1: 400051-000; Maths 4: 400051-003
Description
Select the required time base. Example: ml/s -> time base seconds (s); m³/h -> time base
hours (h).
Only visible if totalization = yes
Options
Second (s), Minute (min), Hour (h), Day (d)
Factory setting
Second (s)
Unit
Navigation
Expert → Application → Maths → Maths x → Totalization → Unit
Direct access code: 400052-00x
Examples: Maths 1: 400052-000; Maths 4: 400052-003