Universal Data Manager
Anhang
77
Factory setting
0
Lock hardware
Navigation
Expert → System → Security → Lock hardware
Direct access code: 100099-000
Description
Device functions/interfaces that are not used can be switched off for security reasons.
Fieldbuses may also be affected in the case of Ethernet or the serial interface!
Please follow the operating instructions.
Options
Ethernet (all ports/services), USB A socket front, USB A socket back, USB B socket front,
Serial interface, SD card
Factory setting
No lock
"External memory" submenu
Navigation
Expert → System → External memory
Description
Contains settings for the external data carrier, amongst other things which data is to be
stored in which format on the external data carrier.
Save as
Navigation
Expert → System → External memory → Save as
Direct access code: 140000-000
Description
"Protected format": All data is stored in a manipulation protected encrypted format. This
data can only be visualized by using our software package. "Open format": data is stored in
a CSV format, this can be opened by a number of different programs (for e.g. MS Excel)
(Attention: no manipulation security).
Options
Protected format, Open format (*.csv)
Factory setting
Protected format
SD card