Universal Data Manager
Anhang
129
Navigation
Expert → Application → Limits → Set point x → Identifier
Direct access code: 450015-0xx
Examples: Set point 1: 450015-000; Set point 30: 450015-029
Description
Name of the set point for identification purposes.
User entry
Text (max. 16 characters)
Factory setting
Limit x
Set point
Navigation
Expert → Application → Limits → Set point x → Set point
Direct access code: 450003-0xx
Examples: Set point 1: 450003-000; Set point 30: 450003-029
Description
Limit value in the set process unit, e.g. in °C, m³/h
User entry
Number (max. 10 digits)
Factory setting
0
Hysteresis (abs.)
Navigation
Expert → Application → Limits → Set point x → Hysteresis (abs.)
Direct access code: 450004-0xx
Examples: Set point 1: 450004-000; Set point 30: 450004-029
Description
The alarm condition is only canceled when the signal has changed into the normal
operation range by the preset value.
User entry
Number (max. 8 digits)
Factory setting
0
Time delay
Navigation
Expert → Application → Limits → Set point x → Time delay
Direct access code: 450005-0xx
Examples: Set point 1: 450005-000; Set point 30: 450005-029
Description
In order to be interpreted as an alarm the signal must exceed or undercut the preset value
by at least the time set up.
User entry
Number (max. 5 digits)