Universal Data Manager
Anhang
89
Description
Enter the end of the zoom range here.
• The zoom can also be set outside the measuring range. The only restriction is that
the start and end of the zoom may not be identical.
• If the signal or the range is changed, the zoom is corrected if it no longer fits the
measuring range.
• The zoom end can also be smaller than the zoom start. The device will automatically
rotate the values on the display.
User entry
Number (max. 8 digits)
Factory setting
Depends on the input signal selected
Damping
Navigation
Expert → Inputs → Universal inputs → Universal input x → Damping
Direct access code: 220008-0xx
Examples: Universal input 1: 220008-000; Universal input 12: 220008-011
Description
Factory default setting: 0.0 s. The more unwanted interference there is on the
measurement signal the higher the value that should be entered here. Result: Fast changes
will be damped/suppressed.
Only visible if signal = current, voltage, resistance temperature detector or thermocouple
User entry
0 to 9
999.9 s
Factory setting
0
For resistance temperature detectors and thermocouples: 0.2s
Comparison point
Navigation
Expert → Inputs → Universal inputs → Universal input x → Comparison point
Direct access code: 220013-0xx
Examples: Universal input 1: 220013-000; Universal input 12: 220013-011
Description
Intern: Compensation of the voltage error by measuring the terminal temperature.
Extern: Compensation of the voltage error by using an external controlled comparison
measurement point.
Only visible if signal = thermocouple
Options
Internal, External
Factory setting
Internal
Comparison temp.