ACS-CONTROL-SYSTEM GmbH
l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
120
Anhang
Universal Data Manager
120
Description
Description of condition change from low to high. Event text is stored (e.g. Start filling).
Only visible if the result is = control input or state
User entry
Text (max. 22 characters)
Event text H->L
Navigation
Expert → Application → Maths → Maths x → Event text H->L
Direct access code: 400012-00x
Examples: Maths 1: 400012-000; Maths 4: 400012-003
Description
Description of condition change from high to low. Event text is stored (e.g. Stop filling).
Only visible if the result is = control input or state
User entry
Text (max. 22 characters)
Record duration
Navigation
Expert → Application → Maths → Maths x → Record duration
Direct access code: 400013-00x
Examples: Maths 1: 400013-000; Maths 4: 400013-003
Description
The duration between "On" and "Off" can be recorded. The duration is appended to the "Off"
event text (<hhhh>h<mm>:<ss>).
Power outage times do not affect the duration. If the digital channel was "on" before the
power outage and is still "on" after the power outage, the duration continues.
Only visible if the result is = control input or state
Options
No, Yes
Factory setting
No
Zoom start
Navigation
Expert → Application → Maths → Maths x → Zoom start
Direct access code: 400016-00x
Examples: Maths 1: 400016-000; Maths 4: 400016-003
Description
If the whole value range is not used, you can configure the lower value of the required
section here. The zoom has no influence on the storage.
Only visible if the result is = instantaneous value
User entry
Number (max. 8 digits)
Factory setting
0