ACS-CONTROL-SYSTEM GmbH
l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
114
Anhang
Universal Data Manager
114
Factory setting
Not used
Unit address
Navigation
Expert → Communication → Modbus Slave → Unit address
Direct access code: 480001-000
Description
Enter the device address where it should be possible to reach this device in the bus.
Only visible if Modbus = RS485
User entry
1 to 247
Factory setting
1
Port
Navigation
Expert → Communication → Modbus Slave → Port
Direct access code: 480004-000
Description
Port via which the Modbus protocol can be activated.
Only visible if Modbus = Ethernet
User entry
Number (max. 5 digits)
Factory setting
502
Timeout
Navigation
Expert → Communication → Modbus Slave → Timeout
Direct access code: 150210-000
Description
Time within which measured values must be received via fieldbus (otherwise an error will
be set). Not relevant if only measured values are read out.
User entry
1 to 99
Factory setting
10
"Serial interface" submenu
Navigation
Expert → Communication → Modbus Slave → Serial interface