Universal Data Manager
Anhang
127
Navigation
Expert → Application → Signal analysis → Analysis x
Direct access code: 44000x-000
Examples: Analysis 1: 440000-000; Analysis 4: 440003-000
Description
For the set timeframe, determines the minimum, maximum and average value or
quantities and operating times.
If the "Externally controlled" option is to be used, a digital input or a maths channel
must be set to "Function = Control input" and "Action = Start/stop analysis x".
Only analysis 1 can be configured; analyses 2-4 are permanently set to daily analysis,
monthly analysis and annual analysis
Options
Switched off, Externally controlled, 1min, 2min, 3min, 4min, 5min, 10min, 15min, 30min,
1h, 2h, 3h, 4h, 6h, 8h, 12h
Factory setting
Switched off
Synchron. time
Navigation
Expert → Application → Signal analysis → Synchron. time
Direct access code: 440004-000
Description
Time for completing the signal analysis.
If, for example, 07:00 is set up then the daily analysis will run from 07:00 of the actual day
until 07:00 of the following day.
User entry
Time
Factory setting
00:00
Reset to zero
Navigation
Expert → Application → Signal analysis → Reset to zero
Direct access code: 440005-000
Description
Reset analysis.
Note: should only be executed after the device has taken over the setup.
Options
Please select, Analysis x, Totalizer, All
Factory setting
Please select
Reset channel
Navigation
Expert → Application → Signal analysis → Reset channel
Direct access code: 440010-000