Description
Determining the correction values to balance measurement tolerances.
Proceed as follows:
• Measure the current value at the lower measurement range.
• Measure the current value at the upper measurement range.
• Enter the lower and upper target and actual value.
Offset
Navigation
Expert → Inputs → Universal inputs → Universal input x → Measured value
correction → Offset
Direct access code: 220050-0xx
Examples: Universal input 1: 220050-000; Universal input 12: 220050-011
Description
This offset is only effective on the analog input signal (no maths / bus channels).
Only visible if signal = resistance thermometer detector or thermocouple
User entry
Number (max. 8 digits)
Factory setting
0
Correction RPT
Navigation
Expert → Inputs → Universal inputs → Universal input x → Measured value
correction → Correction RPT
Direct access code: 220057-0xx
Examples: Universal input 1: 220057-000; Universal input 12: 220057-011
Description
Rear panel temperature correction value for this analog input (only required for
thermocouples).
Only visible/editable if the service code has been entered.
Only visible if signal = resistance thermometer detector or thermocouple
User entry
Number (max. 8 digits)
Factory setting
0
Range start
Target value