Technical Data
Universal Data Manager
60
Interface, communication
connection data
USB ports (standard):
1 x USB port type A (host)
A USB 2.0 connection is available on a shielded USB A socket at the front of the device. A
USB stick, for example, can be connected to this interface as a storage medium. An
external keyboard or USB hub may also be connected.
1 x USB port type B (function)
A USB 2.0 connection is available on a shielded USB B socket at the front of the device.
This can be used to connect the device for communication with a laptop, for example.
Ethernet interface (standard):
Ethernet interface on back, 10/100 Base-T, plug type RJ45. The Ethernet interface can be
used to integrate the device via a hub or switch into a PC network (TCP/ IP Ethernet). A
standard patch cable (e.g. CAT5E) can be used for the connection. Using DHCP, the device
can be fully integrated into an existing network without the need for additional
configuration. The device can be accessed from every PC in the network. Normally only the
automatic assignment of the IP address must be configured at the client. When the device
is started, it can automatically retrieve the IP address, subnet mask and gateway from a
DHCP server. If a DHCP is not used, these settings must be made directly in the device
(depends on the network to which the device is to be connected). Two Ethernet function
LEDs are located on the rear of the device.
Serial RS232/RS485 interface (option):
A combined RS232/RS485 connection is available on a shielded SUB D9 socket at the rear
of the device. This can be used for data or program transfer and to connect a modem. For
communication via modem, we recommend an industrial modem with a watchdog
function.
• The following baud rates are supported: 9600, 19200, 38400, 57600, 115200
• Max. line length with shielded cable: 2 m (6.6 ft) (RS232), or 1000 m (3281 ft) (RS485)
Only one interface can be used at any one time (RS232 or RS485).
15.5 Performance characteristics
Response time
Input
Output
Time [ms]
Current, voltage, pulse
Relay
≤ 550
RTD
Relay
≤ 1150
TC
1)
Relay
≤ 1550
Cable open circuit detection, current input
Relay
≤ 1150
Cable open circuit detection, RTD, TC
Relay
≤ 5000
Digital input
Relay
≤ 350
HART input
Relay
Non-deterministic
1)
If internal measuring point temperature compensation is used, otherwise values as for voltage
Reference operating
conditions
Reference temperature
25 °C (77 °F) ±5 K
Warm-up period
120 min.
Humidity
20 to 60 % rel. humidity